General Operating Conditions

The following conditions must be observed if the fieldbus components are to function without error.

Environmental conditions

Operation

The components may not be used without additional protection in the following locations:

in difficult environments, such as where there are corrosive vapors or gases, or high dust levels

in the presence of high levels of ionizing radiation

Condition

Permissible range

Permissible ambient temperature range during operation

0°C ... +55°C

Permissible relative humidity during operation

95 %, no condensation

Installation position

variable

Vibration resistance

conforms to EN 60068-2-6

Shock resistance

conforms to EN 60068-2-27, EN 60068-2-29

EMC resistance burst

conforms to EN 61000-6-2

ESD emission

conforms to EN 61000-6-4

Transport and storage

Condition

Permissible range

Permissible ambient temperature range during storage

-25 °C ... +85°C

Permissible relative humidity

95 %, no condensation

Free fall

up to 1 m in the original packaging

Protection classes and types

Condition

Permissible range

Protection class in accordance with IEC 536 (VDE
0106, Part 1)

A protective conductor connection to the mounting rail
is necessary!

Protection class according to IEC 529

IP20 (protection against contact with a standard test
finger)

Protection against foreign objects

Less than 12 mm in diameter

Protection against water

No protection