General operating conditions, Environmental conditions, Operation – BECKHOFF BC3150 User Manual
Page 107: Transport and storage, Protection classes and types
Safety Instructions
Fieldbus Components
105
General Operating Conditions
The following conditions must be observed if the fieldbus components are to function without error.
Environmental conditions
Operation
The components may not be used without additional protection in the following locations:
•
in difficult environments, such as where there are corrosive vapors or gases, or high dust levels
•
in the presence of high levels of ionizing radiation
Condition
Permissible range
Permissible ambient temperature range during operation
0°C ... +55°C
Permissible relative humidity during operation
95 %, no condensation
Installation position
variable
Vibration resistance
conforms to EN 60068-2-6
Shock resistance
conforms to EN 60068-2-27, EN 60068-2-29
EMC resistance burst
conforms to EN 61000-6-2
ESD emission
conforms to EN 61000-6-4
Transport and storage
Condition
Permissible range
Permissible ambient temperature range during storage
-25 °C ... +85°C
Permissible relative humidity
95 %, no condensation
Free fall
up to 1 m in the original packaging
Protection classes and types
Condition
Permissible range
Protection class in accordance with IEC 536 (VDE
0106, Part 1)
A protective conductor connection to the mounting rail
is necessary!
Protection class according to IEC 529
IP20 (protection against contact with a standard test
finger)
Protection against foreign objects
Less than 12 mm in diameter
Protection against water
No protection