Technical data, Technical data - bcxx50 – BECKHOFF BC3150 User Manual
Page 13

Safety Instructions
Fieldbus Components
11
Technical Data
Technical Data - BCxx50
Technical data
BCxx5x
Processor
16 bit micro-controller
Diagnostic LEDs
2 x power supply, 2 x K-Bus
Configuration and programming software
TwinCAT PLC
Fieldbus
interface
BC3150
BC5150
BC5250
BC8150
-
Fieldbus
PROFIBUS DP
CANopen
DeviceNet
- Serial ADS
- KS8000 Protocol
- ModbusRTU
- ModbusASCII
-
Interfaces
Serial interface
COM1 (RS232 for configuration and programming, automatic baud rate detection
9600/19200/38400/57600 baud)
Terminal Bus (K-
Bus)
64 (255 with K-Bus extension)
Technical data
BC3150
BC5150
BC5250
BC8150
-
Digital peripheral signals
2040 inputs/outputs
Analog peripheral signals
1024 inputs/outputs
Configuration possibility
via TwinCAT or the controller
Maximum fieldbus byte
number
depending on fieldbus
Maximum number of bytes
- PLC
2048 bytes of input data, 2048 bytes of output data
Bus connection
D-sub, 9-pin
Open Style Connector, 5 pin
D-sub, 9-pin
-
Power supply (Us)
24 V
DC
(-15%/+20%) To meet the UL requirements use a 4 A fuse or a power
supply that has to satisfy NEC class 2!
Input current (Us)
60 mA + (total K-Bus current)/4
Starting current
approx. 2.5 x continuous current
K-Bus current (5 V)
maximum 1000 mA
Power contact voltage
(Up)
maximum 24 V
DC
Power contact current load
(Up)
maximum 10 A
Recommended fuse (Up)
≤
10 A
Dielectric strength
500 V
rms
(power contact / supply voltage / fieldbus)
Weight
approx. 100 g
Dimensions (W x H x D)
approx. 44 mm x 100 mm x 68 mm