Local process image task 1 port 801, Register port 100 – BECKHOFF BC3150 User Manual
Page 76
Safety Instructions
74
Fieldbus Components
ADS Services
Local process image task 1 port 801
Data can be read from and written to the local process image. If it is necessary for outputs to be written, it is
important to ensure that they are not used by the local PLC, because the local controller will overwrite these values.
The data is not associated with a watchdog, and therefore must not be used for outputs that would have to be
switched off in the event of a fault.
Index group
Meaning
Index offset (value range)
0xF020
Inputs
0...2047
0xF030
Outputs
0...2047
0x4020
Flags
0...4095
ADS services
AdsServerAdsState
Data type (read only)
Meaning
String
Start - the local PLC is running
Start - the local PLC is stopped
AdsServerDeviceState
Data type (read only)
Meaning
INT
0 – Start - the local PLC is running
1 – Stop - the local PLC is stopped
AdsServerType
Data type (read only)
Meaning
String
BX PLC Server
Register port 100
The ADS port number in the Bus Terminal Controller for register communication is fixed, being set at 100.
Index offset (value range)
Index group
Hi-Word
Low Word
Meaning
0 [READ ONLY]
0..127
0..255
Registers in the Bus Coupler
High word, table number of the Bus Coupler
Low word, register number of the table
1-255
0-3
1-255
Register of the Bus Terminal
High word, channel number
Low word, register number of the Bus Terminal
Note
Note when reading the register that the time out for the ADS block is set to a time longer
than 1 second.
Note
Note when writing to the registers that the password is set (see the documentation for the
particular Bus Terminal).