Bus cable: length, assignment

The maximum length of cable which can be used depends on the selected
baud rate. The following lengths should be understood as the total length
of the main line plus any branch lines.

125 kbaud 500 m
250 kbaud 250 m
500 kbaud 100 m

Length of
Thin Cable
Used
(meters)

100

80

60

40

20

0

0 50 100 150 200 250 300 350 400 450 500

125k baud

250k baud

500k
baud

Length of Thick Cable Used (meters)

L

thick

+ 5 x L

thin

= 500

at 125Kbaud

L

thick

+ 2.5 x L

thin

= 250

at 250Kbaud

L

thick

+ L

thin

= 100

at 500Kbaud

where L

thick

is the length of thick cable and Lthin

is the length of thin cable.

Jacket

Data I nsul ation
Color: B lue

Braid Shi eld

A L/M Y
Shi eld

Data Insul ation
Color: White

DC Pow er I nsulati on
Color: Red

A L /M Y
Shi eld

DC Pow er I nsulati on
Color: Black

Drain Wi re


The cable consists of two shielded wire pairs. One pair carries out the
transmission. The second pair distributes the supply power.

V+

CAN_H

SHIELD

CAN_L

V-

Red P.M.S. #207C

White EIA 395A within wire/cable limits

Blue P.M.S. #297C

Black P.M.S. #426C


Connector wiring information