Technical data – BECKHOFF BK5200 User Manual
Page 14

Basic Principles
14
BK52x0
Technical data
Electrical data
The DeviceNet couplers differ in the level of the facilities they offer. The
fieldbus-specific electrical data is listed in this section. The following data
differs between the Standard, the Economy and the Low-Cost versions
(BK5200, BK5210 and LC5200). Compatibility with DeviceNet is ensured in
all cases, but the Economy and Low-Cost versions have a restricted
number of I/O points. This is why it is not possible to connect anything
other than digital inputs and outputs.
System data
DeviceNet (BK5200, BK5210, LC5200)
Number of I/O modules
64
Transmission medium
Screened, twisted copper wire with power supply, 5-pin
Length of the cable
500 m
250 m
100 m
Transmission rate
125 kbaud
250 kbaud
500 kbaud
Operating modes
Bit Strobe, Polling, Cyclic, Change of State (COS)
Device Net type
Communications adapter
Technical data
BK5200
BK5210
Number of Bus Terminals
64
Digital peripheral signals
256 inputs/outputs
256 inputs/outputs
Analog peripheral signals
128 inputs/outputs
---
Possibility of configuration
Via KS2000 or the controller
Maximum number of bytes
512 bytes input, 512 bytes output
32 bytes input, 32 bytes output
Bus connection
1 x open pluggable connector, 5-pin, included
Power supply
24 V DC (20...29 V DC), via bus cable 11… 25V (conforms to DeviceNet
specification)
Input current
70 mA + (total K-Bus current)/4
500 mA max.
Starting current
approx. 2.5 x continuous current
Recommended back-up fuse
≤ 10 A
K-Bus power supply up to
1750 mA
500 mA
Power contact voltage
24 V DC max.
Power contact current load
10 A max.
Dielectric strength
500 Veff (power contact / supply voltage Bus Coupler)
Weight approx.
150 g
130 g
Operating temperature
0°C ... +55°C
Storage temperature
-25°C ... +85°C
Relative humidity
95% , no condensation
Vibrations/Shock resistance
conforms to IEC 68-2-6/IEC 68-2-27
EMC resistance burst/ESD
conforms to EN 50082 (ESD, burst)/EN 50081
Installation position
any
Protection class
IP20