3 leds of the e-bus power supply unit, 3 leds of the ebus power supply unit – BECKHOFF CX51x0 User Manual
Page 81
Error handling and diagnostics
6.1.3
LEDs of the Ebus power supply unit
After switching on, the power supply immediately checks the connected Bus Terminal configuration. Error
free startup is signaled by the red "I/O ERR” LED being extinguished. If the “I/O ERR” LED blinks, an error
in the area of the terminals is indicated. The error code can be determined from the frequency and number of
blinks. This permits rapid rectification of the error.
Display
LED
Meaning
Us 24 V
Power supply for the CPU module
The LED lights green if the power
supply is correct.
Up 24 V
Power supply for terminal bus. The
LED lights green if the power supply
is correct.
L/A
off
Ebus not connected
on
Ebus connected / no data traffic
flashing
Ebus connected / data traffic on the
Ebus.
CX51x0
81