Error handling and diagnostics

6.1.3

LEDs of the E­bus power supply unit

After switching on, the power supply immediately checks the connected Bus Terminal configuration. Error­
free start­up is signaled by the red "I/O ERR” LED being extinguished. If the “I/O ERR” LED blinks, an error
in the area of the terminals is indicated. The error code can be determined from the frequency and number of
blinks. This permits rapid rectification of the error.

Display

LED

Meaning

Us 24 V

Power supply for the CPU module
The LED lights green if the power
supply is correct.

Up 24 V

Power supply for terminal bus. The
LED lights green if the power supply
is correct.

L/A

off

E­bus not connected

on

E­bus connected / no data traffic

flashing

E­bus connected / data traffic on the
E­bus.

CX51x0

81