Seconds UPS
Hold USB
Options: Enable / Disable
Switches off the power supply for the USB ports in UPS mode.
Delay
Options: 0…255 seconds
Start delay with which the SUPS is loaded.
SUPS Firmware Version
Firmware version
Current Power Source
Power supply status: Online / Battery
Battery Load Level
Charge state in percent (n% Cap. (n={0...100}) describes the UPS capacity)
Powerfail Counter
Number of power failures
Integration into a PLC
TwinCAT offers special function blocks for integrating the SUPS into a PLC program. These are described
below. From TwinCAT 2.11R3 Build 2247 or TwinCAT 3.1 Build 4018 the required library is integrated in the
installation. For older versions the library TcSUPS_51x0.lib has to be copied into the TwinCAT library
directory.