beautypg.com

BECKHOFF CX51x0 User Manual

Page 79

background image

Error handling and diagnostics

LEDs for K­bus diagnostics

Error code

Error code argu­
ment

Description

Remedy

Persistent, continuous
flashing

EMC problems

­ Check power supply for
overvoltage or undervoltage
peaks

­ Implement EMC measures

If a K­Bus error is present, it
can be localized by a restart of
the power supply (by switching
it off and then on again)

3 pulses

0

K­bus command error

­ No Bus Terminal inserted

­ One of the Bus Terminals is
defective; halve the number of
Bus Terminals attached and
check whether the error is still
present with the remaining Bus
Terminals. Repeat until the
defective Bus Terminal is
located.

4 pulses

0

K­Bus data error, break
behind the power supply

Check whether the n+1 Bus
Terminal is correctly connected;
replace if necessary.

n

Break behind Bus Terminal
n

Check whether the Bus End
Terminal 9010 is connected.

5 pulses

n

K­bus error in register
communication with Bus
Terminal n

Exchange the nth bus terminal

6 pulses

0

Error at initialization

Exchange Bus Coupler

1

Internal data error

Perform a hardware reset on
the Bus Coupler (switch off and
on again)

8

Internal data error

Perform a hardware reset on
the Bus Coupler (switch off and
on again)

7 pulses

0

Process data lengths of the
set and actual
configurations do not
correspond

Check configuration and
terminals for consistency

Error code argument

The number of pulses indicates the position of the last Bus Terminal before the fault. Passive Bus Terminals,
such as a power feed terminal, are not included in the count.

In the case of some errors, rectification does not cause the power supply to leave the blink sequence. The
power supply can only be restarted by switching its supply voltage off and on again.

The CX51xx recognizes these terminals automatically on scanning, reads out the terminal types and
automatically places them in the System Manager.

CX51x0

79

Version 1.0