beautypg.com

9 rs232 connections (cx51x0-n030) – BECKHOFF CX51x0 User Manual

Page 39

background image

Mounting and wiring

4.9

RS232 connections (CX51x0­N030)

The CX51x0­N030 system interface provides an RS232 interface, COM1 (X300). It is implemented on a 9­
pole Sub­D pin contact strip. If more than one interface is required, the system can be extended with the
required number of serial interfaces using the terminal bus (K­ or E­bus) and Bus Terminals (KL/EL6001).
The pin assignment is shown at the bottom of the page.

The maximum baud rate on both channels is 115 kbit. The interface parameters are set via the operating
system or from the PLC program.

RS232 COM interface (connector)

Pin assignment of the COM interface

PIN

Signal

Type

Description

2

RxD

Signal in

Receive Data

3

TxD

Signal out

Transmit Data

5

GND

Ground

Ground

7

RTS

Signal out

Ready to Send

8

CTS

Signal in

Clear to Send