beautypg.com

Instructions, Regulator 1, Regulator 2 – Basler Electric AVC63-7F User Manual

Page 4: Regulator 3, Avc63-7f

background image

Publication

9302800994

Revision

D

Instructions

Date

03/12

Page

4 of 4

Figure 4. Typical Shunt-Pow ered Interconnection

(Delta Connection)

Note: This is a partial drawing of Figure 3.

Figure 5. Typical Auxiliary Winding Pow ered Interconnection

Figure 7. Operational Test

Figure 6. Reactive Differential (Cross Current) Compensation

CT Interconnection

A

B

C

E1

3

AVC63-7F

P0029-04

03-01-05

GENERATOR

480 Vac L-L

(277 Vac L-N)

50/60 HZ

4

E3

480 VAC

240 VAC

Item not supplied by Basler Electric Co.

1

1

A

B

C

FIELD

EXCITER

OPEN TO PARALLEL

CLOSE FOR SINGLE UNIT

UNIT/PARALLEL SWITCH

RHEOSTAT

VOLT. ADJ.

REMOTE

1.5K

2W

CW

7

6

COM

50

E1

2

1

3

F+

F-

AVC63-7F

P0029-02

03-20-12

GENERATOR

400 - 480 VAC

50/60 HZ

3

4

E3

5A SEC NOMINAL

PARALLELING CT

TO LOAD

OR

CIRCUIT

BREAKER

4

2

2

2

1

1

1

2

3

4

AUXILIARY

WINDING

5

5

Phase rotation A-B-C.

Item not supplied by Basler Electric Co.

If remote voltage adjust is not used, short terminals 6 and 7 together.

Short terminals 50 and COM together for 50 Hz operation. Leave unconnected for 60 Hz

operation.

The secondary winding of a sensing transformer must be grounded as closely to the

transformer as practical. When interconnecting more than one transformer, ensure that

the secondary winding of only one transformer is grounded.

10 OHM

10 WATT

LIGHT BULB

120 V

240 VAC

7

6

3

E1

F+

F-

AVC63-7F

P0029-03

03-01-05

4

E3

480 VAC

NOTES
1. When more than three generators are to be paralleled,

continue connections as shown.
2. Paralleling CT polarities are shown with ABC phase rotation.

When connected in cross-current, external resistors may be

required to improve reactive load sharing among generators using

regulators with dissimilar current input burdens. Use the following

table as a guide.

The secondary winding of a sensing transformer must be

grounded as closely to the transformer as practical. When

interconnecting more than one transformer, ensure that the

secondary winding of only one transformer is grounded.

3

A

B

C

GENERATOR

1

CT

E1

2

1

Regulator 1

4

E3

A

B

C

GENERATOR

2

CT

E1

2

1

Regulator 2

4

E3

A

B

C

GENERATOR

3

CT

E1

2

1

Regulator 3

4

E3

3

3

3

P

00

04

-2

3

03

-1

4-

12

4

4

Voltage Regulator

CT Burden

2.5 VA

10 VA

25 VA

External Resistor Value

(not considering lead length)

Not required

0.3 ohms, 15 W

0.9 ohms, 50 W