beautypg.com

Instructions – Basler Electric AVC63-7F User Manual

Page 2

background image

Publication

9302800994

Revision

D

Instructions

Date

03/12

Page

2 of 4

Reactive Differential Compensation
On parallel reactive differential compensation applications

a contact should be used to short out the paralleling CT

secondary when that generator is not paralleled to the bus.

If the switch is not used, a voltage droop will be introduced

into the system. This is due to the unloaded generator

parallel CT not supplying its compensating signal, but

allowing a voltage drop to occur across it. Lack of this

shorting contact will also cause the voltage of the incoming

generator to fluctuate prior to paralleling. Ideally, this

contact is an auxiliary on the circuit breaker contactor that

opens when the circuit breaker is closed.
For reactive differential compensation, connect each CT to

its respective regulator. Then connect the finish of the first

CT to the start of the second CT, the finish of the second

CT to the start of the third CT, etc. Continue until all CT’s

are connected in series. The final step will be to connect

the finish of the last CT to the start of the first CT. (See

Figure 6).
Reactive differential compensation cannot be used when

paralleled with the utility or any infinite bus. If this

compensation system is used, a switching circuit must be

used to convert the system to a reactive droop

compensation system. Contact the factory for additional

information.
OPERATION
General
The following procedures provide instructions for setting

up, starting, operating, and adjusting the AVC 63-7F

Voltage Regulator. Symptoms of problems occurring during

startup that result from incorrect regulator adjustment and

certain generator system problems that resemble faulty

regulation, are included together with possible solutions.
Preliminary Setup
To prevent damage to the regulator, complete the following

steps before proceeding with system startup.
1. Verify that the voltage regulator specifications conform

to the generator system requirements.

2. Ensure that the regulator has been installed and

connected in accordance with the paragraphs on

installation.

Operation at Reduced Speeds
During periods of prime mover idling, use the shutdown

switch to remove power from the regulator.
System Startup
1. Perform preliminary setup as described in the above

paragraphs.

2. Start the prime mover and bring up to rated speed.

Result: Voltage should build up. If not, perform field

flashing.

3. Slowly adjust VOLT adjustment or external voltage

adjust rheostat until the generator output voltage

reaches the nominal value.

4. Apply and remove load to check stability.
5. Check the regulator under normal operating

conditions.
Result: If regulation is not within range, verify the prime

mover is at rated speed.

6. Reduce generator frequency to approximately 5 Hz

below nominal.
Result: Generator output voltage should decrease at

desired frequency.

Adjustments

When the regulator is operated with the generator for the

first time, the polarity of the residual magnetism may not be

correct or of sufficient magnitude. If the residual voltage at

terminals 3 and 4 is greater than 6 Vac, replace the

regulator. If generator residual voltage is less than 6 Vac at

terminals 3 and 4, shut down the prime mover and proceed

with the following steps.

Field Flashing

CAUTION

Do not flash the field with the generator in motion. The

regulator may be damaged.

1. With the prime mover at rest, apply a dc source

(ungrounded), of not more than 48 Vdc, to terminals

F+ (positive) and F- (negative) in series with a limiting

resistor. Use one ohm of resistance for each volt from

the dc power source with a power rating of at least one

watt per ohm. EXAMPLE: If using a 24 Vdc source,

use a 24 ohm, 24-watt resistor.

2. Allow the field to be flashed for approximately ten

seconds before removing the dc source.

3. If voltage buildup does not occur after performing

steps 1 and 2, verify the polarity of the dc source used

in steps 1 and 2 and perform again.

The AVC 63-7F underfrequency adjust is factory preset to

cause an average 2 volt drop in the generator’s line input

voltage to the regulator when the frequency is between

54.5 and 55.5 Hz (for 60 Hz applications). For 50 Hz

applications, the frequency roll-off is factory preset to

between 44 and 46 Hz. To reset the frequency roll-off,

proceed as follows:

Frequency Roll-Off Adjustment

1. Adjust the prime mover rpm to the desired frequency

compensation (corner frequency roll-off) point.

2. Adjust the front panel FREQ control CW until the

output voltage starts to drop off.

3. Bring the prime mover up to rated speed. The output

voltage should return to normal.

An oscilloscope or other voltage recording device should

be used if a stability setting is desired that will provide the

fastest possible voltage response with good generator

stability.

Stability Adjustment

1. Rotation of the front panel STAB control in the

clockwise (CW) direction will slow response time.

2. Rotation of the front panel STAB control in the counter-

clockwise (CCW) direction will speed response time. If

rotated too far CCW, the generator voltage may

oscillate (hunt).

3. Rotate the front panel STAB control CCW until the

system starts oscillating and then rotate CW just past

the point where oscillation occurred.