beautypg.com

Instructions, Avc63-7f – Basler Electric AVC63-7F User Manual

Page 3

background image

Publication

9302800994

Revision

D

Instructions

Date

03/12

Page

3 of 4

1. Installation of a jumper across terminals 6 and 7 allows

the internal (front panel) VOLT adjustment to vary the

generator nominal voltage over the range shown in the

Specifications.

Voltage Adjustment

2. A 1,500 ohm, 2 watt rheostat may be connected to

terminals 6 and 7. This will allow approximately ±10%

adjustment via the remote, 1,500 ohm rheostat.

The droop adjustment allows for adjustment of the amount

of droop, which will occur in the generator output voltage

for a given amount of reactive load current. A CT should be

selected which will supply the AVC with 3 to 5 amperes of

current with rated load and power factor on the generator.

With 5 amperes of current supplied by the CT, at 0.8 power

factor, the amount of droop can be adjusted from 0 to 6%

of nominal generator voltage.

Droop Adjustment

1. Determine the amount of droop desired; 3% to 5% is

common. Adjust the droop potentiometer fully CCW.

2. Bring the generator up to rated speed and rated

voltage. Apply full load at rated power factor.

3. Adjust the droop potentiometer until the desired

amount of droop is achieved.

OPERATIONAL TEST
To operationally test any AVC 63-7F, refer to Figure 7 and

perform the following steps.
1. Connect the voltage regulator as shown in Figure 7

and apply 240 Vac.

2. Adjust the front panel VOLT control fully counter-

clockwise (CCW).
Result: Observe that the lamp does not light.

3. Adjust the front panel VOLT control fully clockwise

(CW).
Result: Observe that the lamp is now lit.

4. Adjust the front panel VOLT control until the lamp just

goes out.

Regulator operation is satisfactory if the above results are

obtained. Stability, however, must be tested with the

generator and regulator operating.

Figure 1. Typical AVC63-7F Frequency Compensation Curves





Figure 2. AVC63-7F Dimensions



Figure 3. Typical Shunt-Pow ered Interconnection

(Wye Connection)

A

B

C

FIELD

EXCITER

OPEN TO PARALLEL

CLOSE FOR SINGLE UNIT

UNIT/PARALLEL SWITCH

RHEOSTAT

VOLT. ADJ.

REMOTE

1.5K

2W

CW

7

6

COM

50

E1

2

1

3

F+

F-

AVC63-7F

P0029-01
03-20-12

GENERATOR

480 Vac L-L

(277 Vac L-N)

50/60 HZ

3

4

E3

5A SEC NOMINAL

PARALLELING CT

TO LOAD

OR

CIRCUIT

BREAKER

4

2

2

2

1

1

1

2

3

4

N

5

5

Phase rotation A-B-C.

Item not supplied by Basler Electric Co.

If remote voltage adjust is not used, short terminals 6 and 7 together.

Short terminals 50 and COM together for 50 Hz operation. Leave unconnected for 60 Hz

operation.

The secondary winding of a sensing transformer must be grounded as closely to the

transformer as practical. When interconnecting more than one transformer, ensure that

the secondary winding of only one transformer is grounded.