beautypg.com

Instructions, Avc63-7, Regulator 1 – Basler Electric AVC63-7 User Manual

Page 4: Regulator 2, Regulator 3, 4 of 4

background image

Publication

9302800991

Revision

B

Instructions

Date

03/12

Page

4 of 4

Figure 3. Interconnections, Typical Shunt-Pow ered

Figure 4. Interconnections, Typical Auxiliary Winding Pow ered

Figure 6. Interconnections, Operational Test

Figure 5. Interconnections, Reactive Differential (Cross-

Current) Compensation

A

B

C

FIELD

EXCITER

OPEN TO PARALLEL

CLOSE FOR SINGLE UNIT

UNIT/PARALLEL SWITCH

RHEOSTAT

VOLT. ADJ.

REMOTE

1.5K

2W

CW

7

6

COM

50

E1

2

1

3

F+

F-

AVC63-7

P0004-21.vsd

03-14-12

GENERATOR

200 - 240 VAC

50/60 HZ

3

4

E3

5A SEC NOMINAL

PARALLELING CT

TO LOAD

OR

CIRCUIT

BREAKER

4

2

2

2

1

1

1
2

3
4

Phase rotation A-B-C.
Item not supplied by Basler Electric Co.
If remote voltage adjust is not used, short terminals 6 and 7 together.
Short terminals 50 and COM together for 50 Hz operation. Leave unconnected for

60 Hz operation.

5

The secondary winding of a sensing transformer must be grounded as closely to

the transformer as practical. When interconnecting more than one transformer,

ensure that the secondary winding of only one transformer is grounded.

5

A

B

C

FIELD

EXCITER

OPEN TO PARALLEL

CLOSE FOR SINGLE UNIT

UNIT/PARALLEL SWITCH

RHEOSTAT

VOLT. ADJ.

REMOTE

1.5K

2W

CW

7

6

COM

50

E1

2

1

3

F+

F-

AVC63-7

P0004-22.vsd

03-14-12

GENERATOR

200 - 240 VAC

50/60 HZ

3

4

E3

5A SEC NOMINAL

PARALLELING CT

TO LOAD

OR

CIRCUIT

BREAKER

4

2

2

2

1

1

1
2

3
4

Phase rotation A-B-C.
Item not supplied by Basler Electric Co.
If remote voltage adjust is not used, short terminals 6 and 7 together.
Short terminals 50 and COM together for 50 Hz operation. Leave unconnected for

60 Hz operation.

AUXILIARY

WINDING

5

The secondary winding of a sensing transformer must be grounded as closely to the

transformer as practical. When interconnecting more than one transformer, ensure

that the secondary winding of only one transformer is grounded.

5

10 OHM

10 WATT

LIGHT BULB

120 V

240 VAC

7

6

E1

3

F+

F-

AVC63-7

P0004-24

02-10-05

4

E3

NOTES
1. When more than three generators are to be paralleled,

continue connections as shown.
2. Paralleling CT polarities are shown with ABC phase rotation.

When connected in cross-current, external resistors may be

required to improve reactive load sharing among generators using

regulators with dissimilar current input burdens. Use the following

table as a guide.

The secondary winding of a sensing transformer must be

grounded as closely to the transformer as practical. When

interconnecting more than one transformer, ensure that the

secondary winding of only one transformer is grounded.

3

A

B

C

GENERATOR

1

CT

E1

2

1

Regulator 1

4

E3

A

B

C

GENERATOR

2

CT

E1

2

1

Regulator 2

4

E3

A

B

C

GENERATOR

3

CT

E1

2

1

Regulator 3

4

E3

3

3

3

P

00

04

-2

3

03

-1

4-

12

4

4

Voltage Regulator

CT Burden

2.5 VA

10 VA

25 VA

External Resistor Value

(not considering lead length)

Not required

0.3 ohms, 15 W

0.9 ohms, 50 W