beautypg.com

Instructions – Basler Electric AVC63-7 User Manual

Page 2

background image

Publication

9302800991

Revision

B

Instructions

Date

03/12

Page

2 of 4

Figures 4 and 5 show the correct CT polarity for ABC phase

rotation sequence. If the phase rotation sequence is ACB,

the CT secondary leads must be interchanged.
Reactive Droop Compensation
For reactive droop compensation, connect the CT to its

respective regulator as shown on Figures 4 and 5.
A unit-parallel switch shorts the parallel CT secondary to

prevent any droop signal from being injected into the

regulating system during single unit operation. The switch

may not be required on parallel droop compensation

applications where a voltage drop is not objectionable.
Reactive Differential Compensation
On parallel reactive differential compensation applications a

contact should be used to short out the paralleling CT

secondary when that generator is not paralleled to the bus.

If the switch is not used, a voltage droop will be introduced

into the system. This is due to the unloaded generator

parallel CT not supplying its compensating signal, but

allowing a voltage drop to occur across it. Lack of this

shorting contact will also cause the voltage of the incoming

generator to fluctuate prior to paralleling. Ideally, this contact

is an auxiliary on the circuit breaker contactor that opens

when the circuit breaker is closed.
For reactive differential compensation, connect each CT to

its respective regulator. Then connect the finish of the first

CT to the start of the second CT, the finish of the second CT

to the start of the third CT, etc. Continue until all CT’s are

connected in series. The final step will be to connect the

finish of the last CT to the start of the first CT. (See Figure

5).
Reactive differential compensation cannot be used when

paralleled with the utility or any infinite bus. If this

compensation system is used, a switching circuit must be

used to convert the system to a reactive droop

compensation system. Contact the factory for additional

information.
OPERATION
The following procedures provide instructions for setting up,

starting, operating, and adjusting the AVC 63-7 Voltage

Regulator. Symptoms of problems occurring during startup

that result from incorrect regulator adjustment and certain

generator system problems that resemble faulty regulation

are included together with possible solutions.
Preliminary Setup
To prevent damage to the regulator, complete the following

steps before proceeding with system startup.
1. Verify that the voltage regulator specifications conform

to the generator system requirements.

2. Ensure that the regulator has been installed and

connected in accordance with the paragraphs on

installation.

Operation at Reduced Speeds
During periods of prime mover idling, use the shutdown

switch to remove power from the regulator.
System Startup
1. Perform preliminary setup as described in the above

paragraphs.

2. Start the prime mover and bring up to rated speed.

Result: Voltage should build up. If not, perform field

flashing.

3. Slowly adjust VOLT adjustment or external voltage

adjust rheostat until the generator output voltage

reaches the nominal value.

4. Apply and remove load to check stability.
5. Check the regulator under normal operating conditions.

Result: If regulation is not within range, verify the prime

mover is at rated speed.

6. Reduce generator frequency to approximately 5 Hz

below nominal.
Result: Generator output voltage should decrease at

desired frequency.

Adjustments
Field Flashing. When the regulator is operated with the

generator for the first time, the polarity of the residual

magnetism may not be correct or of sufficient magnitude. If

the residual voltage at terminals 3 and 4 is greater than 6

Vac, replace the regulator. If generator residual voltage is

less than 6 Vac at terminals 3 and 4, shut down the prime

mover and proceed with the following steps.

CAUTION

Do not flash the field with the generator in motion.

Damage to the regulator may result.

1. With the prime mover at rest, apply a dc source

(ungrounded), of not more than 48 Vdc, to terminals F+

(positive) and F– (negative) in series with a limiting

resistor. Use one ohm of resistance for each volt from

the dc power source with a power rating of least one

watt per ohm.
EXAMPLE: If using a 24 Vdc source, use a 24 ohm, 24

watt resistor.

2. Allow the field to be flashed for approximately 10

seconds before removing the dc source.

3. If voltage buildup does not occur after performing steps

1 and 2, verify the polarity of the dc source used in

steps 1 and 2 and perform again.

The AVC 63-7 underfrequency adjust is factory preset to

cause an average 1 volt drop in the generator's line input

voltage to the regulator when the frequency is between 54.5

and 55.5 Hz (for 60 Hz applications). For 50 Hz applications,

the frequency roll-off is factory preset to between 44 and 46

Hz. To reset the frequency roll-off, proceed as follows:

Frequency Roll-Off Adjustment

1. Adjust the prime mover rpm to the desired frequency

compensation (corner frequency roll-off) point.

2. Adjust the front panel FREQ control CW until the output

voltage starts to drop off.

3. Bring the prime mover up to rated speed. The output

voltage should return to normal.

An oscilloscope or other voltage recording device should be

used if a stability setting is desired that will provide the

fastest possible voltage response with good generator

stability.

Stability Adjustment

1. Rotation of the front panel STAB control in the

clockwise (CW) direction will slow response time.