Bit unsigned integer, object 102, Bit unsigned integer, object 102 -18, Bit unsigned integer -18 – Basler Electric BE1-851E DNP3 Protocol User Manual
Page 38

8-Bit Unsigned Integer, Object 102
Table 5-12 is the point list for Object 102, and lists the 8-Bit Unsigned Integer Points. Note that this object
has only variation 1 and cannot be requested with default variation 0.
Table 5-12. Object 102, 8-Bit Unsigned Integer Points
8-Bit Unsigned Integer
Object Number: 102
Variations Supported: 1
Request Function Codes supported: 1 (read)
Index
Description
0 - 9
Model Number
10 - 28
Application Software Version Number and Date
29 - 47
Boot Software Version Number and Date
48 - 61
Serial Number
62 - 83
Style Number
84 - 99
Part Number
100 - 131
Relay ID
132 - 163
Station ID
Explanation:
Each point represents one character of a particular string.
Example: To read the Model Number, which is “BE1-851E”, the returned read value for points 0 to 9 are:
Point
0
1
2
3
4
5
6
7
8
9
Read Value in
ASCII format
B
E
1
-
8
5
1
Null
Null
Null
Object 102 is not included in Class 0 poll response.
5-18
BE1-851E DNP Protocol
9289900792 Rev C