Analog output status points and control blocks, Analog output status points and control blocks -14, Table 5-7. breaker failure status format -14 – Basler Electric BE1-851E DNP3 Protocol User Manual
Page 34: Table 5-8. system status -14

15. BF status is the bit mapped variable with format as described in Table 5-7. Delta of 1 deviation will
cause en event.
Table 5-7. Breaker Failure Status Format
Value / Bit Mask (hex)
Description
0001
Breaker Operation Control State {1=Breaker Operation Enabled;
0= Breaker Operation Disabled}
0002
Breaker State {1=Breaker Opened; 0= Breaker Closed}
16. Delta of 1 bit (any change) will cause an event.
17. Read values for Hardware Output Control is 1 = Enabled, and 0=Disabled.
18. Read values for x43 AUX Virtual Switch Logic Mode are 0 for Disabled, 1 = ON/OFF PULSE, 2 =
ON/OFF, and 3= OFF/MOMENTARY ON.
19. Read values for Setting Group Mode is 0= Disabled, 1=discrete select, and 2= binary select.
Setting groups can be controlled via DNP object 12 if value is 1 or 2.
20. Read values for 101 Breaker Control Switch Mode is 0=Disabled and 1=Enabled.
21. Latched Targets Status format is described in Table 5-5 under Note 6 to Table 5-4. Delta of 1
deviation will cause an event. Latched Targets Status can be reset via object 41 point 7.
22. BE1-851E Relay System Status is represented as 4 part, 16-bit mapped variables. The four part
System Status is described in Table 5-8. (For more information, see the BE1-851E Instruction
Manual, Section 6, Reporting and Alarm Functions). Delta of 1 deviation will cause an event.
Table 5-8. System Status
Value/Bit Mask (hex) Part 1 Description
Part 2 Description Part 3 Description
Part 4 Description
0001h
50 Phase Tripped
BF Picked Up
Virtual Output A
Input Contact 1
0002h
150 Phase Tripped
51 Phase Picked Up Virtual Output 1
Input Contact 2
0004h
50 Neutral Tripped
51 Neutral Picked UP Virtual Output 2
Input Contact 3
0008h
150 Neutral Tripped
51 Q Picked Up
Virtual Output 3
Input Contact 4
0010h
50Q Tripped
62 Tripped
Virtual Output 4
101 TRIP
0020h
150Q Tripped
162 Tripped
Virtual Output 5
101 CLOSE
0040h.
BF Tripped
43
Virtual Output 6
101 SLIP CONTACT
0080h
51 Phase Tripped
143
Virtual Output 7
HMI Reset Key
0100h
51 Neutral Tripped
243
Virtual Output 8
Logic Alarm
0200h
51 Q Tripped
343
Virtual Output 9
Major Alarm
0400h
50 Phase Picked Up 79 Close
Virtual Output 10 Minor Alarm
0800h
150 Phase Picked Up 79 Enabled
Virtual Output 11 Output 1 Trip Coil Monitor
1000h
50 Neutral Picked Up 79 Lockout
Virtual Output 12 Setting Group 0
2000h
150 Neutral Picked Up 79 Reclose Fail
Virtual Output 13 Setting Group 1
4000h
50Q Picked Up
79 Block Output
Virtual Output 14 Setting Group 2
8000h
150Q Picked Up
Always False (zero) Virtual Output 15 Setting Group 3
Analog Output Status Points and Control Blocks
Table 5-9 lists both the Analog Status Points (Object 40) and the Analog Output Control Blocks (Object
41). It is important to note that Analog Output Status Points are not included into Class 0.
The Return Status Value for object 41 for all control operations may be 6 (hardware problem) due to a
value out of range, or a relay internal state. One of the reasons for rejection may be if another
communication port or front panel HMI is actively programming. For more information, see the BE1-851E
Instructional Manual, Section 10, Human-Machine Interface.
5-14
BE1-851E DNP Protocol
9289900792 Rev C