Basler Electric BE1-851E DNP3 Protocol User Manual
Page 14

OBJECT
REQUEST
(BE1-851E will parse)
RESPONSE
(BE1-851E will respond with)
Object
No.
Variation
No.
Description
Function
Codes (dec)
Qualifier Codes
(hex)
Function
Codes (hex)
Qualifier Codes
(hex)
30
4
16-Bit Analog Input Without
Flag
1 (read)
00,01 (start- stop)
06 (no range)
07,08 (limited qty)
17,28 (index)
81
00,01 (start-stop)
17,28 (index)
32
0
Analog Change Event
(Variation 0 is used to request
default variation)
1 (read)
06 (no range)
07,08 (limited qty)
32
1
(default -
see note 1)
32-Bit Analog Input without
time
1 (read)
06 (no range)
07,08 (limited qty)
81
17,28 (index)
32
2
16-Bit Analog Input without
time
1 (read)
06 (no range)
07,08 (limited qty)
81
17,28 (index)
32
3
32-Bit Analog Input with time 1 (read)
06 (no range)
07,08 (limited qty)
81
17,28 (index)
32
4
16-Bit Analog Input with time 1 (read)
06 (no range)
07,08 (limited qty)
81
17,28 (index)
40
0
Analog Output Status -
(Variation 0 is used to request
default variation)
1
00,01 (start-stop)
06 (no range)
07,08 (limited qty)
17,28 (index)
40
1
32-bit Analog Output Status
1 (read)
00,01 (start-stop)
06 (no range)
07,08 (limited qty)
17,28 (index)
81
00,01 (start-stop)
17,28 (index)
40
2
(default -
see note 1)
16-bit Analog Output Status
1 (read)
00,01 (start-stop)
06 (no range)
07,08 (limited qty)
17,28 (index)
81
00,01 (start-stop)
17,28 (index)
41
1
32-bit Analog Output Block
3 (select)
4 (operate)
5 (direct op)
6 (dir op noack)
00,01 (start-stop)
07,08 (limited qty)
17,28 (index)
81
echo of request
41
2
16-bit Analog Output Block
3 (select)
4 (operate)
5 (direct op)
6 (dir op noack)
00,01 (start-stop)
07,08 (limited qty)
17,28 (index)
81
echo of request
50
1
Time and Date
1 (read)
2 (write)
00,01 (start-stop)
06 (no range or all)
07 (limited qty=1)
08 (limited qty)
17,28 (index)
81
00,01 (start-stop)
17,28 (index)
60
1
Class 0 Data (Note 1) (Note 4) 1 (read)
06 (no range or all)
81
60
2
Class 1 Data
1 (read)
06 (no range or all)
07,08 (limited qty)
81
60
3
Class 2 Data
1 (read)
06 (no range or all)
07,08 (limited qty)
81
60
4
Class 3 Data
1 (read)
06 (no range or all)
07,08 (limited qty)
81
80
1
Internal Indications
2 (write)
00 (start-stop)
(index must=7)
102
1
8-Bit Unsigned Integer (Note
2)
1 (read)
00,01 (start- stop)
06 (no range)
07,08 (limited qty)
17,28 (index)
81(response) 00,01 (start-stop)
17,28 (index)
No Object(function code only)
(See Note 3)
13 (cold restart)
No Object(function code only)
(See Note 3)
14 (warm
restart)
No Object (function code only) 23 (delay meas)
3-2
BE1-851E DNP Protocol
9289900792 Rev C