Table 5-6. reclose status format -13 – Basler Electric BE1-851E DNP3 Protocol User Manual
Page 33

Value/Bit Mask
Part 1 Description
Part 2 Description
0200h
150TB
151B
0400h
150TC
151C
0800h
150TN
151N
1000h
150TQ
151Q
2000h
spare
spare
4000h
spare
spare
8000h
spare
spare
7.
Reclose Status are bit mapped variables that report the state of the recloser shot counter prior to
the fault that triggered the fault (see format in Table 5-6).
Table 5-6. Reclose Status Format
Value/Bit Mask
Description
0001h
Recloser active
0002h
Recloser Reset
0004h
Reclose Max Timing
0008h
Reclose Failure
0010h
Reclose Lockout
0020h
Reclose Wait
0040h
Reclose Enable
0080h
Reclose Max Enable
0100h
Reclose Fail Enable
0200h
Reclose Wait Enable
0400h
Reclose Timing 1
1000h
Reclose Timing 2
2000h
Reclose Timing 3
4000h
Reclose Timing 4
8000h
Reclose Timing Fail
8. Fault Clearing Time is time in milliseconds from 0 to 60,000.
9. Breaker Operate Time is time in milliseconds from 0 to 60,000.
10. A number of recorded oscillographic records per fault (read value of this point) can be 1 or 2.
11. Time presented in relay internal format: part 1 contains days (1 to 65,535) and part 2 milliseconds
(1 to 86,400,000) since January 1, 1984.
12. Point represents assigned phase accumulated breaker pole duty as a centipercent of the
maximum duty (DMAX) that the breaker contacts can withstand before they need service.
Breaker Accumulated Duty for Phase A, B, and C is calculated as ΣI or ΣI
2
. This is defined by the
Breaker Contact Duty Operation Mode 0/1/2 entered via the ASCII protocol command SB-DUTY.
DMAX is defined through the same SB-DUTY command (for more information, see the BE1-851E
Instruction Manual, Section 4, Protection and Control). Value range is from 0 to 20,000 where
20,000 represents 200% of DMAX. Delta of 20 centipercent will cause an event. This point can be
changed via object 41. See the paragraph for Analog Output Control Blocks, Note 9.
13. This is the number of recorded breaker operations (0 - 99,999). If the operations counter exceeds
99,999, the counter will wrap back to zero. This value can be changed via object 41, point 15 to
any value from 0 to 99,999. Delta of 1 will cause an event.
14. Selected Fault Summary Report contains fault data for fault number defined by the value of Analog
Output Status (object 40) point 21 “Fault Number for Selected Fault Summary Report”.
9289900792 Rev C
BE1-851E DNP Protocol
5-13