Analog output status points -15, Analog output blocks -15, Table 5-9 – Basler Electric BE1-851E DNP3 Protocol User Manual
Page 35

Table 5-9. Analog Output Status Points and Control Blocks
Analog Output Status Points
Object Number: 40
Variations Supported: 1, 2
Request Function Codes supported: 1 (read)
Default Variation Reported When Variation 0 Requested: 1 (32-Bit Analog Output Status)
Analog Output Blocks
Object Number: 41
Variations Supported: 1, 2
Request Function Codes supported: 3(select), 4(operate), 5(direct operate), 6 (direct operate, noack)
Index
Description
Notes
0
Hardware Output Logic Control Mode
1,2
1
43 Aux Virtual Switch Logic Mode
1,3
2
143 Aux Virtual Switch Logic Mode
1,3
3
243 Aux Virtual Switch Logic Mode
1,3
4
343 Aux Virtual Switch Logic Mode
1,3
5
Active Setting Group Control Mode
1,4
6
101 Breaker Control Switch Mode
1,5
7
Target Status Reset Control
6
8
Major Alarms Reset
7
9
Minor Alarms Reset
7
10
Logic Alarms Reset
7
11
Relay Trouble Alarms Reset
8
12
Breaker Accumulated Duty for Phase A
9
13
Breaker Accumulated Duty for Phase B
9
14
Breaker Accumulated Duty for Phase C
9
15
Breaker Operation Counter
10
16
Peak Demand Current Since Reset - Phase A
11
17
Peak Demand Current Since Reset - Phase B
11
18
Peak Demand Current Since Reset - Phase C
11
19
Peak Demand Current Since Reset - Neutral
11
20
Peak Demand Current Since Reset - Negative Sequence
11
21
Fault Number for Selected Fault Summary Report
12
22
Synchronization Time Period
13
23
Current Dead Band
14
24
‘Control Relay Output Blocks’ Table Selection
15
Notes for Table 5-9:
1. This data is a setting and takes effect after being saved to non-volatile memory.
Procedure of saving data to non-volatile memory is performed only once per request for all points
requested to be changed through function Operate(4), Direct Operate(5) or Direct Operate
Noack (6).
Saving to a non-volatile memory is not implemented per point basis because it would significantly
prolong requested message processing time and cause response time-out. It is important to note
that object 12 (Binary Output Status ) points from 0 to 23 can be successfully controlled only if
their function blocks mode are enabled in the time of parsing. This is the reason that
in the same
9289900792 Rev C
BE1-851E DNP Protocol
5-15