3 - implementation table, Dnp implementation table, Section 3 • implementation table -1 – Basler Electric BE1-851E DNP3 Protocol User Manual
Page 13

SECTION 3 • IMPLEMENTATION TABLE
DNP Implementation Table
Table 3-1 identifies which object variations, function codes, and qualifiers the BE1-851E DNP supports in
both request messages and in response messages.
Static (non-change-event) object requests sent with qualifiers 00, 01, 06, 07, or 08 will be responded to
with qualifiers 00 or 01. Static object requests sent with qualifiers 17 or 28 will be responded to with
qualifiers 17 or 28.
Change-event objects are always responded to with qualifiers 17 and 28.
Table 3-1. BE1-851E DNP Implementation Table
OBJECT
REQUEST
(BE1-851E will parse)
RESPONSE
(BE1-851E will respond with)
Object
No.
Variation
No.
Description
Function
Codes (dec)
Qualifier Codes
(hex)
Function
Codes (hex)
Qualifier Codes
(hex)
1
0
Binary Inputs - (Variation 0 is
used to request default
variation)
1 (read)
00,01 (start- stop)
06 (no range)
07,08 (limited qty)
17,28 (index)
1
1
(default -
see note 1)
Single-Bit Binary Input
1 (read)
00,01 (start- stop)
06 (no range)
07,08 (limited qty)
17,28 (index)
81
(response)
00,01 (start-stop)
17,28 (index)
2
0
Binary Input Change
(Variation 0 is used to request
default variation)
1 (read)
06 (no range)
07,08 (limited qty)
2
1
Binary Input Change without
time
1 (read)
06 (no range)
07,08 (limited qty)
81
(response)
17,28 (index)
2
2
(default -
see note 1)
Binary Input Change with time 1 (read)
06 (no range)
07,08 (limited qty)
81
(response)
17,28 (index)
10
0
Binary Output - (Variation 0 is
used to request default
variation)
1 (read)
00,01 (start- stop)
06 (no range)
07,08 (limited qty)
17,28 (index)
10
2
(default -
see note 1)
Binary Output Status
1 (read)
00,01 (start- stop)
06 (no range)
07,08 (limited qty)
17,28 (index)
81
00,01 (start-stop)
17,28 (index)
12
1
Control Relay Output Block
3 (select)
4 (operate)
5 (direct op)
6 (dir op Noack)
00,01 (start-stop)
07,08 (limited qty)
17,28 (index)
81
echo of request
30
0
Analog Input (Variation 0 is
used to request default
variation)
1 (read)
00,01 (start- stop)
06 (no range)
07,08 (limited qty)
17,28 (index)
81(response) 00,01 (start-stop)
17,28 (index)
30
1
32-Bit Analog Input With Flag 1 (read)
00,01 (start- stop)
06 (no range)
07,08 (limited qty)
17,28 (index)
81
00,01 (start-stop)
17,28 (index)
30
2
16-Bit Analog Input With Flag 1 (read)
00,01 (start- stop)
06 (no range)
07,08 (limited qty)
17,28 (index)
81
00,01 (start-stop)
17,28 (index)
30
3
(default -
see note 1)
32-Bit Analog Input Without
Flag
1 (read)
00,01 (start- stop)
06 (no range)
07,08 (limited qty)
17,28 (index)
81
00,01 (start-stop)
17,28 (index)
9289900792 Rev C
BE1-851E DNP Protocol