SECTION 2 • DEVICE PROFILE DOCUMENT
Introduction
Table 2-1 provides a Device Profile Document in the standard format defined in the DNP3 subset
definition document. The table, in combination with the implementation table provided in Section 3 and
the point list tables provided in Section 5, provide a complete application configuration guide for including
the BE1-851E DNP protocol in any DNP environment.
Table 2-1. DNP3 Device Profile Document
DEVICE PROFILE DOCUMENT
Vendor Name: Basler Electric Company
Device Name: BE1-851E Enhanced Overcurrent Protection System
Highest DNP Level Supported:
DNP-L2.
Device Function:
Master Slave
Notable objects, functions, and/or qualifiers supported in addition to the highest DNP levels supported
(the complete list is described in DNP3 Implementation Table):
- For static (non-change-event) object requests, request qualifier codes 00 and 01(start-stop), 07
and 08 limited quantity), and 17 and 28(index) are supported in addition to request qualifier code
06 (no range - or all points).
- Static object requests sent with qualifiers 00,01,06,07, and 08, will be responded to with qualifiers
00 or 01.
- Static object requests sent with qualifiers 17 and 28 will be responded to with qualifiers 17 or 28.
- The read function code for object 102 (8-bit unsigned integer), variation 1, is supported.
- Time period when device requires time-synchronization from the master is configurable via object
41, point 22.
- Dead band for current analog inputs’ events is configurable via object 41, point 23.
- Control Relay Output Blocks may be operated as defined in Table 4 or Table 5. Table selection is
made via object 40/41, point 24.
Maximum Data Link Frame Size (octets):
Transmitted 292
Received 292
Maximum Application Fragment Size (octets):
Transmitted 2048
Received 1024
Maximum Data Link Re-tries:
None
Fixed at
Configurable
Maximum Application Layer Re-tries:
None
Fixed at
Configurable, range ______ to ______
Requires Data Link Layer Confirmation:
Never
Always
Sometimes If 'Sometimes', when?
Configurable If 'Configurable', how?
Requires Application Layer Confirmation:
Never
Always (not recommended)
When reporting Event Data (Slave devices only)
When sending multi-fragment responses (Slave devices only)
9289900792 Rev C
BE1-851E DNP Protocol