Vent requirements, Installation, Altitude considerations – Avalon Firestyles Vashon-1998 to 1999 User Manual
Page 8

8
Installation
(for qualified installers only)
Travis Industries
9 3 5 0 8 1 0 2
0 9 1 0 0 2
Vent Requirements
!
Always maintain the required 1Ó (25 mm) clearance (air space) to combustible materials to prevent a fire
hazard. Do not fill air spaces with insulation.
!
The gas appliance and vent system must be vented directly to the outside of the building, and never
be attached to a chimney serving a separate solid fuel or gas-burning appliance. Each direct vent gas
appliance must use itÕs own separate vent system.
Altitude Considerations
This heater has been tested at altitudes
ranging from sea level to 8,000 feet
(2,400 M). In this testing we have found
that the heater, with its standard orifice,
burns correctly with just an air shutter
adjustment.
!
Failure to adjust the air shutter properly
may lead to improper combustion which
can create a safety hazard. Consult your
dealer or installer if you suspect an
improperly adjusted air shutter.
¥
When the vent passes through a wall,
a wall thimble is required. When the
vent passes through a ceiling, a
support box or firestop is required.
When the vent passes through the
roof, a roof flashing and storm collar
are required. Follow the instructions
provided with the vent (from
Duravent¨) for installing these items.
Use a firestop spacer whenever
passing through a ceiling
(Duravent Part #963)
Vertical Termination
(Duravent Part # 991)
Use a roof flashing and storm collar
whenever passing through the roof
(Duravent Part #953 & #943 or #943S)
8-5/8"
(220 mm)
Use a support box
on exposed vent
Vertical Vent
Requirements
Use a wall thimble
whenever passing
through a wall
(Duravent Part #942)
Horizontal Termination
(Duravent Part #984)
Maintain a minimum 1" (25 mm)
clearance from vent to any combustible
(vent is 6 5/8" (170 mm) diameter)
Minimum
Framing for
wall thimble
Horizontal Vent
Requirements
Minimum framing
for fire stop
8-5/8"
(220 mm)
Maintain a minimum 1"
(25 mm) clearance from
vent to any combustible
(vent is 6 5/8" (170 mm)
diameter)
¥
Use Model GS Direct Vent manufactured by Simpson Dura-Vent
only
(or the Chimney Conversion Kit
- see Addendum #2). Follow the installation instructions included with the vent. For the nearest
Simpson Dura-Vent supplier, call (800) 835-4429. Part numbers and descriptions are listed below.
Straight Lengths
908B
6Ó Pipe Length, Black (interior)
907B
9Ó Pipe Length, Black (interior)
906
12Ó Pipe Length, Galvanized
906B
12Ó Pipe Length, Black (interior)
904
24Ó Pipe Length, Galvanized
904B
24Ó Pipe Length, Black (interior)
903
36Ó Pipe Length, Galvanized
903B
36Ó Pipe Length, Black (interior)
902
48Ó Pipe Length, Galvanized
902B
48Ó Pipe Length, Black (interior)
911B
11Ó to 14 5/8Ó Pipe, Adjustable, Black (interior)
Vent Terminations
981
Snorkel Termination (36Ó rise)
(for basement installations)
982
Snorkel Termination (14Ó rise)
(for basement installations)
984
Horizontal Square Termination
950
Vinyl Siding Standoff
991
Vertical Termination
Elbows
990
90¥ Elbow
990B
90¥ Elbow, Black (interior)
945
45¡ Elbow
945B
45¡ Elbow, Black (interior)
Penetration, Support Parts
942
Wall Thimble
940
Optional Wall Thimble Cover
941
Cathedral Ceiling Support Box
943
Flashing, 0/12 to 6/12 Roof Pitch
943S
Flashing, 7/12 to 12/12 Roof
Pitch
953
Storm Collar
963
Ceiling Firestop
988
Wall Strap
¥
Apply high-temperature silicone to the inner and outer pipe before
assembling the sections (on the male, upper section). This seals the
inner pipe from the outer pipe. Slide the sections together and turn 1/4
turn until the sections lock in place. Install three metal screws through
each joint to lock the outer section in place (see the instructions included
with the vent for further details).
NOTE: You may screw the first section of vent to the appliance.
¥
Horizontal sections require a 1/4Ó rise every 12Ó of travel
Apply a 1/8" (3 mm)
bead of high-
temperature silicone
to the inner and
outer pipe. The
silicone must seal
the inner pipe from
the outer pipe.
Silicone
Silicone
+
Exterior Vent Diameter = 6-5/8Ó , Inner Vent Diameter = 4Ó
¥
Horizontal sections require non-combustible support every 36Ó (e.g.: use plumbing tape)