Operation

3-14

GUPS 2400A

–107 Operation Manual

3.9.6.3

Status Word 2 Format

Table 3

–6 provides the bit position information and definition of the data in Status Word 2.

Bit

Name

Definition

0

Running on Battery

0 = Running on AC
1 = Running on battery

1

Reserved

2

Inverter Keypress

0 = No Keypress Pending
1 = Inverter Keypress Pending

3

System Shutdown

0 = System Operating
1 = System Shutdown

4

Reserved

5

Running on AC Line

0 = Running on Battery
1 = Running on AC Line

6

150% Overload Sense

0 = Normal Operation
1 = 150% Overload Detected

7

Float Timer Time-out

0 = Not Float Charging
1 = Float Timer Time-out

8

Wait to equalize

0 = No Equalization Pending
1 = Waiting To Equalize

9

Pass/Fail System Self-Test

0 = Self Test Failed
1 = Self Test Passed

10

System Down

0 = System Operational
1 = System Is Shutting Down

11

AC Input Line Out of Range

0 = AC Input Line In Range
1 = AC Input Line Out of Range

12

Delayed Event Flag

0 = No Pending Delayed Events
1 = Delayed Event Pending

13

Reserved

14

Reserved

15

Improper Output Voltage

0 = Output Normal
1 = Output Is Low

Table 3

–6. Status Word 2 Data Format