3.9.6

Status Words

The status words may be used to examine the current state of the GUPS 2400A-107, but are
not meant to be used in applications that are time

–critical such as AC line loss detection. The

―Line Loss Detected‖ message sent from the GUPS 2400A-107 (refer to Section 3.9.7), or the
AC Line Loss signal (relay contact closure) will have the quickest response time.

3.9.6.1

Status Word 1 Format

Table 3

–5 provides the bit position information and definition of the data in Status Word 1.

Bit

Name

Definition

0

Over Temperature

0 = Normal Operation
1 = Over Temperature

1

Alarm Sense

0 = Alarm Not Sensed
1 = Alarm Sensed

2

Alarm Silence

0 = Alarm Silence Not Enabled
1 = Alarm Silence Enabled

3

Charger Status

0 = Charger Not On
1 = Charger On

4

Current Overload

0 = Normal Operation
1 = Current Overload

5

Battery Switch

0 = Battery Switch Not On
1 = Battery Switch On

6

Test Mode

0 = Normal Operation
1 = Test Mode

7

Inverter Status

0 = Inverter Not On
1 = Inverter On

8

Output Relay

0 = Output Relay Open
1 = Output Relay Closed

9

Impending Shutdown

0 = Greater then 1 minute
1 = Less then 1 minute

10

Rectifier Slow Start

0 = Normal Operation
1 = Rectifier In Slow Start

11

Equalization Charge

0 = Equalization Charge Not On
1= Equalization Charge On

12

Power Available

0 = Power Not Available
1 = Power Available

13

PWM Soft Start

0 = Normal Operation
1 = Unit In Soft Start Mode

14

Reserved

15

Battery Slow Start

0 = Normal Operation
1 = Battery Slow Start

Table 3

–5. Status Word 1 Data Format