Operation

GUPS 2400A

–107 Operation Manual

3-9

3.9.4.2

Display Calibration Values

En

ter a command ‗k‘ (lowercase K) character to display the calibration constants for the A/D

converter algorithms values. For example:

Calibration Constants:
80 percent current: 32F8

// Output current in hexadecimal

105 percent current: 424B
150 percent current: 50E7
Minimum voltage band: 2000

// Output voltage in hexadecimal

Maximum voltage band: 2100
Battery 200 volts: 0198

// Battery voltage in hexadecimal

Battery bad: 0240
Battery shutdown: 0268
AC line A-B scale factor: 31030

// AC input line voltage scale factors in decimal

AC line B-C scale factor: 31030
AC line C-A scale factor: 31030

Vout rdbk cal: 91.3

// Output voltage readback calibration in

Vout rdbk dvm: 114.5

floating point format

3.9.4.3

Display Status Registers and A/D Values

Enter a command ‗s‘ (lowercase S) character to display the two 16-bit status registers, along
with the A/D values of the AC input voltage, Output voltage, Output current, and
Battery/Charger voltage. For example:

Status word 1: 5540

// 16-bit status flags in hexadecimal

Status word 2: 0283
A/D Values:

// A/D values in floating point and hexadecimal

Output Voltage: 115.0

2314

Output Current: 3.25

0028

Input Voltage A-B: 200.0

4E20

Input Voltage B-C: 200.0

4E20

Input Voltage C-A: 200.0

4E20

Battery Voltage: 190.00

0284

The status word formats are explained in Section 3.9.6.

3.9.4.4

Display Firmware Version Number

Enter a command ‗v‘ (lowercase V) character to display the version number of the firmware.
For example:

Firmware version number: P/N 5152457-01, Rev 2.0