Operation

3-6

GUPS 2400A

–107 Operation Manual


3.

To turn OFF the output, press the OUTPUT ON switch again; the switch has a
alternating ON/OFF action. The unit will shut down (with no AC input present); the
inverter and all control circuits will turn off.


3.8.1

Battery Care and Handling

The battery used in the GUPS 2400A-107 requires proper storage and recharging to maintain
reliability.

During storage, the self-discharge of the battery results in a sulfate coating that builds up on the
plates. This coating reduces the effective surface area of the plates which reduces the available
backup time. Allowing the batteries to self-discharge for too long may result in recharging
problems or in battery degradation.

Storing the battery at low temperatures reduces the level of chemical activity, thus sulphation
takes longer to occur. Reasonable storage times at different temperatures are listed in
Table 3

–2.

Storage Temperature

Storage Time

0°C (32°F)

20 Months

10°C (50°F)

10 Months

20°C (68°F)

5 Months

40°C (104°F)

1½ Months

Table 3

–2. Battery Storage Times

The batteries should be recharged for 72 hours after prolonged storage.

CAUTION!
Failure to recharge the batteries after the storage time may result
in permanent battery degradation.