General Description

1-2

GUPS 2400A

–107 Operation Manual

Battery Recharge Time: 4 hours to 90% full charge following discharge

at 2400VA/1920W and 25°C

Output Voltage: 115V, ±2%

Output Frequency: 60Hz, ±0.1%

Output Current: 20.9A(RMS)

Output Distortion: 2% THD, maximum with linear load

Output Power: 1920W with resistive load;

2400VA/1920W with a reactive load or a non-linear load

Efficiency: 77%

AC to Battery Crossover: 159V, maximum low-line voltage;

232V, minimum high-line voltage


Battery to AC Crossover: 169V, maximum low-line voltage;

232V, minimum high-line voltage


AC Input Voltage Unbalance: 7V (RMS) maximum difference in line voltages

Temperature: 0°C to 40°C (32°F to 104°F), operating;

-40°C to 65°C (-40°F to 149°F), non-operating


Humidity: 5% to 95% non-condensing, operating

Altitude: 0 to 10,000ft, operating;

0 to 40,000ft, 2000ft/min, maximum, non-operating


Dimensions: 7"H x 19"W x 25.1"D,

excluding protrusion of handles, controls, and connectors;
fits standard RETMA rack


Weight: 75lb (34kg), UPS enclosure;

48lb (22kg) battery module;
123lb (56kg) total weight