Ethernet option, Programming procedure, 2b 2c and d – American Time SiteSync IQ User Manual
Page 19

19
© American Time
SiteSync IQ Installation Manual
Ethernet Option
Programming Procedure
u
Configure Communication (Comm) Settings:
Press
P 8 3
to access Comm settings
a. Use the keypad to Enable DHCP or Disable to select static IP entry.
• Press
1
for enable DHCP
• Press
2
for disable DHCP
• Press
O
to accept
• If
1
skip to e
b. Use the keypad to enter the Unit IP Address. This is a static address
assigned by your Network Administrator. Enter preceding zeros as
necessary.
• Press
O
c. Use the keypad to enter the Subnet Mask. Enter preceding zeros as
necessary. This is the subnet mask of your network.
• Press
O
d. Use the keypad to enter the Gateway IP. Enter preceding zeros as
necessary. This is the IP address of your network's Gateway device.
• Press
O
e. Use the keypad to enter the Time Server Address. Enter
preceding zeros as necessary. Press
O
.
OR Press
O
to accept the default set at the factory from the list of
known good Internet Time Servers in Appendix A.
f. Use the keypad to enter the Alternate Time Server Address.
Enter preceding zeros as necessary. Press
O
.
OR Press
O
to accept the default set at the factory from the list of
known good Internet Time Servers in Appendix A.
g. The unit will prompt you to enter the Port Number. This is for Remote
Connect web access and should be set to 0080.
Press
O
to accept the default (80) set at the factory.
h. Press:
OBB
, to return to Main Screen.
v
Sync System Controller with correct time & date:
a. Press:
P1
, to Set Menu Mode.
b. Enter User Lock and press
O
.
c. Press:
9
, to sync the System Controller with Ethernet. Press
>
until
Ethernet option is chosen.
d. Press
8
to sync with Ethernet.
n
Note: If "Ethernet Sync Successful" is displayed, press
OBB
to return
to Main Screen.
If "Ethernet Sync Failed" is displayed, reference the troubleshooting guide.
w
The Ethernet sync option is now configured and will update the time on the
System Controller automatically once each hour at a time preset at the factory.
n
Note: When Ethernet synchronization is working, ETH=S will be displayed on
the screen in small text mode as shown in screen shot
3
. If a synchronization
attempt fails, ETH=N will be displayed.
MON MAR 10 2014
10:38:06 AM USCT
American Time
Status=AUTO ETH=Y
Glossary
Appendix
Troubleshooting
Clock
Installation
System Contr
oller
Installation
Intr
oduction
Turn on the power to the System Controller
n
Note: These settings may already have been
entered using the Startup Wizard.
Comm Menu
Unit IP Address
192.168.001.001
<=BkSp OK=Done
Comm Menu
Enter Subnet Mask
255.255.255.000
<=BkSp OK=Done
Comm Menu
Time Server Address
137.107.013.100
<=BkSp OK=Done
Comm Menu
Enter Port Number
for web access:0080
OK=Done
Comm Menu
Enter Gateway IP
192.168.010.099
<=BkSp OK=Done
1g
1d (example)
1c (example)
1e (example)
1b (example)
1a
Set Menu Mode
Enter User Lock:
xxxx
PROG=EXIT
OK=ENTER
Set Menu Mode
Time Sync Option is
Available: Ethernet
8=Sync now
OK=Set
2b
2c and d
MON MAR 10 2014
10:30:06 AM USCT
American Time
Circts=Auto ETH=S
3
Comm Menu
DHCP
1=Enable
2=Disable Ok=Done
1f
Comm Menu
Alt Time Srvr Addr
173.014.055.009
<=Bksp
Ok=Done