 MOUNTING TO GROUT FILLED CONCRETE BLOCK 
 
IMPORTANT: IT IS THE RESPONSIBILITY OF THE INSTALLER TO 
VERIFY THAT THE WALL SURFACE IS STRUCTURALLY CAPABLE 
OF SUPPORTING THE PRODUCT AND ALL ASSOCIATED SAFETY 
FACTORS AS REQURED BY ALL APPLICABLE CODES AND SAFE 
SUSPENSION PRACTICES. THE INSTALLER SHOULD CONSULT 
WITH A STRUCTURAL ENGINEER PRIOR TO INSTALLATION TO 
INSURE THAT THE WALL SURFACE CAN SUPPORT THE WEIGHT 
OF THE 112/NAT OR 108/NAT AND ALL ASSOCIATED RIGGING 
AND ALL REQUIRED SAFETY FACTORS. THE COMPOSITION OF 
THE WALL STRUCTURE
MUST
BE REVIEWED BY A
STRUCTURAL ENGINEER PRIOR TO INSTALLATION!
NOTE: MOUNTING ON HOLLOW CORE BLOCK(CMU) IS 
NOT PERMTTED! DO NOT MOUNT ON HOLLOW CORE 
BLOCK! 
 
MOUNT ON GROUT FILLED BLOCK ONLY! 
STOP! THE BLOCK SIZE MUST BE 16 INCHES X 8 INCHES 
X 8 INCHES! (OR METRIC EQUIVALENT) DO NOT USE 
SMALLER BLOCK SIZE. DO NOT ATTEMPT TO MOUNT THE 
112NAT OR 108NAT TO SMALLER BLOCK SIZES! 
 
THE BLOCK (CMU) MUST BE ASTM C-90 OR EQUIVALENT! 
 
A TORQUE WRENCH IS REQUIRED FOR THIS 
INSTALLATION! 
 
BRACKET LOCATION ON GROUT FILLED BLOCK WALLS! 
 
The mounting holes in the grout filled concrete block 
MUST be drilled at least 12 inches (305mm) away from any 
edges or openings in the grout filled block wall! DO NOT 
drill the bracket mounting holes in the grout filled CMU 
(concrete masonry unit) block where wall edges or 
openings in the wall are closer then 12 inches (305mm)! 