Afq-4w instruction manual 99 – CIRCUTOR AFQ Series User Manual
Page 99

AFQ-4W
Instruction Manual 99
Name
Type
Function
Address (Hexadecimal)
Minimum load current
Word
R/W
0015
Response
Description
Response in Amps without decimals.
Minimum load current to start the
AFQ-4W
Name
Type Function
Address (Hexadecimal)
AFQ range Word
R/W
0016
Response
Description
25 / 50 / 100 / 150 / 200
Unit range
.
WARNING: DO NOT MODIFY
Name
Type
Function
Address (Hexadecimal)
Configuration code
Word
R/W
0017
Response
14: Complete configuration
25: Enter AFQ-4W configuration
Name
Type
Function
Address (Hexadecimal)
AFQ software version
Word
R
0018
Response
Description
Response format X.XX
AFQ software version
Name
Type
Function
Address (Hexadecimal)
Control algorithm
Word
R/W
0019
Response
Description
1: Frequency mode
2: Temporary mode
Control algorithm selection
Name
Type
Function
Address (Hexadecimal)
Parallel AFQ number
Word
R/W
001A
Bit
Response
Description
0
1
2
No. of AFQ-4W 25A
Numbering from 0 to 7
Number of AFQ-4W installed in parallel.
The value is coded in 16 bits.
Note The consulted unit counts as 1u.,
so the minimum value will be 001 for the
consulted range.
3
4
5
No. of AFQ-4W 50A
Numbering from 0 to 7
6
7
8
No. of AFQ-4W 100A
Numbering from 0 to 7
9
A
B
No. of AFQ-4W 150A
Numbering from 0 to 7
C
D
E
No. of AFQ-4W 200A
Numbering from 0 to 7
F
F:0 No. AFQYY <= 7 units
F: 1 No. AFQYY == 8
where YY: Range of AFQ 25,
50, 100, 150, 200
Flag indication of 8 AFQ-4W of the
same range in parallel