AFQ-4W
52 Instruction Manual
Click on the Lock/Unlock parameters key to lock or unlock the configuration
parameters. (Refer to section 4.3.6)
4.3.2.2.- SELECTIVE FILTERING
Select the harmonics to be filtered on this screen (
Figure 54: Selective filtering screen.
If the unit is configured with the control 1 algorithm (Frequency mode)
(refer to section
4.3.3.- CONFIGURATION OF PARAMETERS
, select the
harmonics you wish to neutralise from the 3rd to the 25th. (3rd, 5th, 7th by
default)
If the unit is configured with the control 2 algorithm (Temporary mode)
4.3.3.- CONFIGURATION OF PARAMETERS
, you can (use
this option only if recommended by your supplier):
• Leave all harmonics unselected. The AFQ-4W will automatically
filter all harmonics from the 3rd to the 50th.
• Select the harmonics NOT to be filtered. The selected harmonics
will not be filtered.
Click on the Main key to open the home screen.
Click on the Back key to return to the work mode screen.
Click on the Lock/Unlock parameters key to lock or unlock the configuration
parameters. (Refer to section 4.3.6)