Function selection – CIRCUTOR AFQ Series User Manual
Page 51

AFQ-4W
Instruction Manual 51
4.3.2.1.- FUNCTION SELECTION
Use this screen (
) to select the functions of the AFQ-4W:
Figure53: Function selection screen.
Harmonic filtering: Current harmonic neutralisation. (This option is enabled by
default.)
Phase balancing: Balancing of the current between phases. (This option is not
enabled by default.)
Reactive compensation: A function that allows the shifting of the cos
Φ to be
compensated. (This option is not enabled by default.)
Function priority Order: The AFQ-4W allows the functions to be prioritised in
the event of filter current saturation by overload. When the “Function priority
order ” function is disabled, priority is given to the current harmonic filtering and
reactive compensation and overload balancing are penalised. If “Function
priority order” is activated, priority is given to current balancing between phases
and reactive current compensation, ahead of harmonic neutralisation. (This
option is not enabled by default.)
Function priority order
P
R
IOR
IT
Y
-
+
OFF
ON
Harmonic filtering
Phase balancing +
reactive compensation
Phase balancing +
reactive compensation
Harmonic filtering
Table 7: Configuration of the order of priorities.
Click on the Main key to open the home screen.
Click on the Back key to return to the work mode screen.