2 electrical characteristics, 3 environmental characteristics, 4 mechanical characteristics – CIRCUTOR FRE Series User Manual
Page 7: Lectrical characteristics, Nvironmental, Haracteristics, Echanical characteristics

FRE / FRES
7 / 20
4.2 Electrical characteristics
- Operating voltage and nominal frequency:
U
n
/ f , listed on the label
- Design voltage:
U
Nn
+ 10% (440 V for 400 V equipment)
- Nominal power and distribution of steps:
Q
n
and composition, (see label)
- Overvoltage factor, p%
Standard 7% ,
Others 14%, 8.2% and 5.67% (see label
)
- Total loss:
Standard 3.5 at 4 W/kvar
- Residual discharge voltage:
75 V after 3 minutes
- Overload capacity:
1.3 . I
n
in all items
- Contact operating voltage:
U
aux
, listed on the label.
NOTE: In general, use a 1.5 mm2 cable to supply external power.
If the label indicates “
Internal” , means that this the auxiliary circuit does not require external power.
- Current Transformer Input:
5 A , (Transformer I
n
/5 A)
NOTE: Minimum cable section 2.5mm2.
- Compliance with Standards
EN-61642 and UNE EN 61921
- Protection elements:
Fuses
Type gL, NH gauge (minimum 1.5 x I
n
)
Reactor thermostat:
90 ºC ±5 ºC
Insulation
3 kV /50 Hz
Breaking capacity
10 A / 250 V
ac
, resistive load
- Capacitor characteristics:
Capacity tolerance:
± 5%
Insulation level from earth:
3 kV /50 Hz
Impulse test:
15 kV , ray type wave 1.2/50 µs
Protection elements:
Internal fuses and over-pressure system
Compliance with Standards
EN 60831
- Reactor characteristics:
Inductor tolerance:
± 5%
Rated voltage
standard 500 V (RMS value)
Saturation current
Standard at 1.4 I
n
, L=5% (
Others for
RBX
)
Level of insulation phases to earth
3 kV /50 Hz; 15kV shockwave 1.2/50 µs
Max. overload Σ(n.I
n
)
2
Permanent 20% ; Transient (1 min) 2 I
n
4.3 Environmental Characteristics
- Capacitor max. temperature
Category C in accordance with EN 60831-1
Maximum for 1h
50 ºC
24h average
40 ºC
Annual average
30 ºC
- Max. temperature of reactors
In accordance with IEC 60076-6
Maximum environmental temperature
60 ºC
Indoor temperature at In
<110 ºC
Protection thermostat
90 ºC
Cabinet ventilation
For Tout > 30 ºC, forced ventilation must
be used for the cabinet
- Maximum relative humidity:
80%
- Altitude:
1000 m (For higher altitudes, always
maintain forced ventilation)
4.4 Mechanical characteristics:
- Protection degree:
Marked on the label:
- Paint
Oven dried epoxy type
- Standard colours
RAL 7035 Grey ; RAL 3005 Maroon