2.3 Application warnings
Capacitor banks with detuned filters can attenuate the remote control signals
transmitted through the network which are used in some countries to connect or
disconnect certain loads or lines. When remote control frequencies close to the
tuning frequency of
FRE or FRES filters are used, blocking filters must be placed in
the supply line, or the tuning frequency of the
FRE /or FRES filters must be
changed.
3
RECEPTION, TRANSPORT, HANDLING AND STORAGE
3.1 Reception protocol
Make sure that the equipment has not been damaged during transport.
Check that the equipment received matches with the order and that its electrical characteristics
are suitable for the grid where it is to be connected.
Check the shipping documentation. The dispatch note number must coincide with the number
marked on the outer part of the unit package.
Unload and transport the equipment in accordance with the instructions in section 3.2
Perform an external and internal visual inspection of the equipment prior to connecting it.
Check that all items on the packing list are present and match with the delivered documentation.
If any discrepancy is detected upon reception, immediately contact the transport
company or CIRCUTOR's after-sales services.
3.2 Transport, loading and unloading, handling and storage
The transport, loading and unloading and handling of the equipment must be
carried out with proper precautions and using the proper manual or mechanical
tools to prevent damaging the equipment.
If the equipment is not to be immediately installed, it must be stored at a location
with a firm and level floor and satifying the storage conditions listed in the technical
characteristics section. It is recommended that the equipment be stored with its
original protective packaging.
To move the equipment a short distance, the unit's floor support profiles facilitate handling with a pallet
jack or forklift.
The centre of gravity of some units may be at a considerable height. Therefore,
when handling with a forklift, it is recommended that the equipment be securely
fastened and that no abrupt operations are made. The equipment should not be
lifted more than 20 cm over the ground.
Fig. 3-1 .-Transport with pallet jack
When unloading and moving the equipment, use a forklift with forks long enough to support the entire
length of the base. In the limit, the forks should be long enough to support at least ¾ of the depth. The