16 instruction manual getest – CIRCUTOR GETEST Series User Manual
Page 16

16
Instruction manual
Getest
Danger: loop resistance too
high, possible connection
error. Check connectons and
ensure nobody is touching the
injection curcuit. Continue?
This is a life-
threatening scenario.
Resistance found is too
high, it may be caused
by bad connections.
Check connection, ensure
nobody is on the are or
touching the
connectors/electrodes/
auxiliary ground, remove stain
from
connectors/electrodes/auxiliary
ground
Warning: Device may not
have enough power for
injecting the required current.
Loop resistance is too high
for the required current.
Continue?
This is a life-
threatening scenario.
Load resistance is too
high for requested
current.
MPC will apply maximun
power, but won’t reach the
requested current value
Error: cannot reach required
current, mains voltage drops
down. Mains supply is unable
to power required current. At
least 20KVA are required.
Continue extrapolating data?
You have requested
more power to the
device than the power
that the mains line may
supply. Power is equal
to the ground resistance
by the square of the
requested current. If
allowed, PDA will
extrapolate the values to
the requested current,
but applying a lower
value.
Plug the MPC unit to a mains
socket connected to a mains
line with lower impedance, or
to a more powerful generator
Warning: Shortcircuit found
at the output. Current limited
to 35 A. Check connections.
Measured resistance is
lower than 0.1
Ω
Check connections. It may be
possible that an conductive
plane is inserted in the ground.
M
ea
su
ri
n
g
Warning: resistance found
higher than 120Ohms. Check
connections. Continue?
This is a life-
threatening scenario.
Load resistance is too
high.
Check connection, ensure
nobody is on the are or
touching the
connectors/electrodes/
auxiliary ground, remove stain
from
connectors/electrodes/auxiliary
ground