4�4�4�5�- Other parameters

The

Read function is implemented for these variables.

Table 8: Modbus variables: Other parameters�

Description

Address

Size

Units

Energy meter model

1)

0xF010

6x16 bits

12 bytes in ASCII format

Serial no

0x2710

32 bits

-

Transformation ratios

Voltage primary

0x044C

32 bits

V (1 decimal place)

Voltage secondary

0x044E

32 bits

V (1 decimal place)

Current primary

0x0450

32 bits

A (1 decimal place)

Current secondary

0x0452

32 bits

A (1 decimal place)

Energy meter firmware version

Higher firmware version

0x0050

16 bits

-

Lower firmware version

0x0051

16 bits

-

Revised firmware version

0x0052

16 bits

-

Communications module firmware version

Higher firmware version

0x0578

16 bits

-

Lower firmware version

0x0579

16 bits

-

Revised firmware version

0x057A

16 bits

-

Note: Some MODBUS variables may not be available depending on the CEM energy meter

coupled to the

CEM M-RS485. See “4.4.4.7.- Available addresses by unit”

(1)

Energy meter model description table, Table 9�

Table 9: Energy meter model description table�

Options

C10 C20 C30

bytes in ASCII

format

Connection mode

2 wires

2

4 wires

4

Accuracy

Class B active / Does not measure

reactive energy

10

Class B active / Class 2.0 reactive

12

Measurement voltage

1x230

E

1x127

B

3x127/220 ... 3x230/400 V

U

3x127/220 V

N

3x230/400 V

Q

3x57/100 ... 3x230/400 V

V

3x57/100 V

L

3x63.5/110 V

M

Current measurement

Shunt 10(60) A

S4

Shunt 5(65) A

S7

Direct 10(60)A

D4

Direct 5(65)A

D7

Transformer 5(10) A

T5

Transformer 5(6) A

T6

16

CEM M-RS485