Write commands – CIRCUTOR CEM-M-RS-485 User Manual

Page 13

background image

The unit will respond to us with the next frame:

Address

Function

No� of bytes

Serial no�

CRC

01

04

04

XXXX XXXX

CRC

Note: The values are shown in hexadecimal.

The number of requested logs must be the same as the size of the variable requested.

It is possible to read several consecutive addresses, if the request meets the correct format.

4�4�3�- WRITE COMMANDS

The

CEM M-RS485 supports integer type write functions: 0x01.

The unit's Modbus variables are specified in

Table 4

.

Example: Changing the Modbus address of peripheral 01 to the address

0x000A

.

We will send the following Modbus frame:

Address

Function

Initial log

Log no�

No� bytes

Data

CRC

01

10

03E8

0001

02

000A

CRC

The unit will respond to us with the next frame:

Address

Function

Initial log

Log no�

CRC

01

10

03E8

0001

CRC

Note: The values are shown in hexadecimal.

The number of logs to write must be the same as the size of the variable that is being

accessed.

It is possible to write several consecutive addresses, if the request meets the correct format.

13

Instruction Manual

CEM M-RS485