Table 3:LINK LED, colour codes�

LINK LED

Colour

Status

Flashing red

Unit not linked

Steady green

Unit linked

COMS LED: Flashes with each transmission made by the RS-485 port.

4.3.-

OPTICAL COMMUNICATIONS PORT

The unit has an optical serial communications port on its right side, in accordance with the UNE

EN 62056-21:2003 standard, in order to communicate with other devices in the

CEM family.

4.4- RS-485 COMMUNICATIONS

4�4�1�- MODBUS PROTOCOL

The

MODBUS protocol is a communication standard in the industry that enables the network

connection of multiple units, where there is a master and multiple slaves. Within the

MODBUS

protocol the

CEM M-RS485 uses the RTU (Remote Terminal Unit) mode.

In RTU mode, message starts and ends are detected with silences of at least 3.5 characters,

and the 16-bit CRC error-detection method is used.

The

MODBUS functions implemented in the unit are:

Functions 03 and 04. Reading logs.

Function 10. Writing multiple logs.

4�4�2�- READ COMMANDS

The

CEM M-RS485 supports integer type read functions: 0x03 and 0x04.

The unit's Modbus variables are specified in

Table 4

.

Example: Reading of the unit's serial number with peripheral number 01.

We will send the following Modbus frame:

Address

Function

Initial log

Log no�

CRC

01

04

2710

0002

CRC

12

CEM M-RS485

Instruction Manual