4�4�4�3�- Operating time, cost and KgCO2 atmospheric emissions
The
Read function is implemented for these variables.
Table 6: Modbus variables: Operating time, costs and KgCO
2
Description
Address
Size
Units
Cost of the partial consumption
0x00C0
32 bits
-
KgCO2 atmospheric emissions of the partial consumption 0x00C2
32 bits
-
Hours of partial operation
0x00C4
32 bits
( 1 decimal place)
Hours of total operation
0x00C6
32 bits
( 1 decimal place)
Note: Some MODBUS variables may not be available depending on the CEM energy meter
coupled to the
CEM M-RS485. See “4.4.4.7.- Available addresses by unit”
4�4�4�4�- Instantaneous values
The
Read function is implemented for these variables.
Table 7: Modbus variables: Instantaneous values�
Description
Address
Size
Units
Phase 1 voltage
0x0732
32 bits
V (1 primary decimal place)
Phase 2 voltage
0x0734
32 bits
V (1 primary decimal place)
Phase 3 voltage
0x0736
32 bits
V (1 primary decimal place)
Phase 1 current
0x0738
32 bits
A (2 primary decimal places)
Phase 2 current
0x073A
32 bits
A (2 primary decimal places)
Phase 3 current
0x073C
32 bits
A (2 primary decimal places)
Phase 1 cos φ
0x073E
32 bits
2 decimal places
Phase 2 cos φ
0x0740
32 bits
2 decimal places
Phase 3 cos φ
0x0742
32 bits
2 decimal places
Phase 1 active power
0x0746
32 bits
W
Phase 2 active power
0x0748
32 bits
W
Phase 3 active power
0x074A
32 bits
W
Total active power
0x074C
32 bits
W
Phase 1 reactive power
0x074E
32 bits
var
Phase 2 reactive power
0x0750
32 bits
var
Phase 3 reactive power
0x0752
32 bits
var
Total reactive power
0x0754
32 bits
var
Phase 1 apparent power
0x0756
32 bits
VA
Phase 2 apparent power
0x0758
32 bits
VA
Phase 3 apparent power
0x075A
32 bits
VA
Total apparent power
0x075C
32 bits
VA
Note: Some MODBUS variables may not be available depending on the CEM energy meter
coupled to the
CEM M-RS485. See “4.4.4.7.- Available addresses by unit”