4�4�4�- VARIABLES MODBUS
All
MODBUS map addresses are hexadecimal.
4�4�4�1�- Configuration variables
The
Read and Write functions are implemented for these variables.
Table 4:Modbus configuration variables CEM M-RS485.
Description
Address
Size
Valid data range
Default
value
Modbus address
0x03E8
16 bits
1 ... 254
1
Transmission speed
(Baudrate)
0x03E9
16 bits
0: 9600, 1:19200, 2: 38400
0: 9600
Communications configuration
0x03EA
16 bits
0: 8N1 ( 8 bits - No parity -1 stop bit)
1: 8E1 ( 8 bits - Even parity -1 stop bit)
2: 8O1 ( 8 bits - Odd parity -1 stop bit)
3: 8N2 ( 8 bits - No parity -2 stop bit)
4: 8E2 ( 8 bits - Even parity -2 stop bit)
5: 8O2 ( 8 bits - Odd parity -2 stop bit)
0
Impulse output type
0x0080
16 bits
0: Active energy, 1: Reactive energy
0
Impulse output weight
0x0081
16 bits
Wh/impulse 0 ... 99999
-
Cost per kWh
0x00B0
32 bits
0.0000 ... 9999.9999 with 4 decimal places
of resolution
-
KgCO
2
0x00B2
32 bits
0.0000 ... 9.0000 with 4 decimal places of
resolution
-
Note: Some MODBUS variables may not be available depending on the CEM energy meter
coupled to the
CEM M-RS485. See “4.4.4.7.- Available addresses by unit”
4�4�4�2�- Energy
The
Read function is implemented for these variables.
Table 5: Modbus variables: Energy
Description
Address
Size
Units
Total values
Imported active energy
0x0000
32 bits
Wh
Exported active energy
0x0002
32 bits
Wh
Q1 reactive energy
0x0004
32 bits
varh
Q2 reactive energy
0x0006
32 bits
varh
Q3 reactive energy
0x0008
32 bits
varh
Q4 reactive energy
0x000A
32 bits
varh
Partial values
Partial imported active energy
0x0030
32 bits
Wh
Partial exported active energy
0x0032
32 bits
Wh
Q1 partial reactive energy
0x0034
32 bits
varh
Q2 partial reactive energy
0x0036
32 bits
varh
Q3 partial reactive energy
0x0038
32 bits
varh
Q4 partial reactive energy
0x003A
32 bits
varh
Note: Some MODBUS variables may not be available depending on the CEM energy meter
coupled to the
CEM M-RS485. See “4.4.4.7.- Available addresses by unit”
14
CEM M-RS485
Instruction Manual