beautypg.com

CIRCUTOR CVM-BD Series User Manual

Page 24

background image

-- Supply network analyzers CVM-BD-420-4 & CVM-BD-420-8 -- M98132301-20 --- Page Nº 23


5.7.- Maximum power demand

Push the key "display" and the following screens will appear by display:

1.- DEMAND PERIOD ( 1 to 60 min.) ("SET Per xx")
2.- PARAMETER TO CONTROL ("SET Pd xx")

Three phase active power

kW III

21

Three phase apparent power kVA III

26

Three phase average current AavIII

20


Value of power integrated during the programmed demand period.

3.- CLEAR MAXIMUM VALUE IN MEMORY
("CLr Pd xx") no or YES

PROGRAMMING MODE:
-

"max" key: allows choosing the different available options.

-

"min" key: allows the validation of the blinking digit and go forward to the

next digit (only for the "SET Per xx" option).
- To pass to the next option press "display".

If you don't want to modify anything, just press the "display" key three times without
modifying any value.

-

Display

: If you program the MAXIMUM POWER DEMAND option, parameter

35

, the following appears by display (depending on the pressed key):

display

Present value of the demand power meter (Sliding Window,
according to the set demand period) updated every second.

max

MAXIMUM integrated value (since last reset)

min

HOUR : MINUTE DAY : MONTH (“”HH.MM DD/MM”)
when this maximum has occurred