Code

8 bit binary, hexadecimal 0-9, A-F.
2 hexadecimal characters contained in each 8-bit field in
the message.

Bits per byte

8 data bits.

Field Check-Error

CRC Type (Cyclical Redundancy Check).


Modbus functions used:

Function 01

Reading the status of the relays.


Function 03 and 04

Reading n Words (16 bits-2 bytes). Function used for
reading the electrical parameters that the CVM-MINI is
measuring. All electrical parameters are long with 32 bits,
because of this two Words are required to request each
parameter.

(4 bytes - XX XX XX XX)


Function 05

Writing a relay.

6.1 MODBUS memory map

PARAMETER

SYMBOL

Instant

Maximum

Minimum

Units

Voltage phase

V L1

00-01

60-61

C0-C1

V x10

Current

A L1

02-03

62-63

C2-C3

mA

Active power

kW L1

04-05

64-65

C4-C5

w

Reactive power

Kvar L1

06-07

66-67

C6-C7

w

Apparent power

kV·A L1

4A-4B

AA-AB

10A-10B

Power factor

PF L1

08-09

68-69

C8-C9

x 100

Voltage phase

V L2

0A-0B

6A-6B

CA-CB

V x10

Current

A L2

0C-0D

6C-6D

CC-CD

mA

Active power

kW L2

0E-0F

6E-6F

CE-CF

w

Reactive power

Kvar L2

10-11

70-71

D0-D1

w

Apparent power

kV·A L2

4C-4D

AC-AD

10C-10D

w

Power factor

PF L2

12-13

72-73

D2-D3

x 100

Voltage phase

V L3

14-15

74-75

D4-D5

V x10

Current

A L3

16-17

76-77

D6-D7

mA

Active power

kW L3

18-19

78-79

D8-D9

W

Reactive power

Kvar L3

1A-1B

7A-7B

DA-DB

W

Apparent power

kV·A L3

4E-4F

AE-AF

10E-10F

w

Power factor

PF L3

1C-1D

7C-7D

DC-DD

x 100

Temperature

ºC

50-51

B0-B1

110-111

ºC x 10