beautypg.com

Troubleshooting – Nexen SC100 964420 User Manual

Page 14

background image

FORM NO. L-21163-C-0808

14

TROUBLESHOOTING

WEB GUIDE SENSORS

Z

ERO

A

DJUSTMENT

1. Apply Power to the SC100.
2. Cover the sensor window completely with an

opaque material (See Figure 20).

3. Connect a voltmeter to terminals 5 (+) and 6 (-).
4. Adjust Z1 until the voltmeter reads 0.025 VDC.
5. Connect a voltmeter to terminals 7 (+) and 8 (-).
6. Adjust Z2 until the voltmeter reads 0.025 VDC.

S

PAN

A

DJUSTMENT

1. Uncover the sensor window.
2. Connect a voltmeter to terminals 5 (+) and 6 (-).
3. Adjust S1 until the voltmeter displays 10.0 VDC.

NOTE: If using one sensor, skip steps 4 through 6.

4. Connect a voltmeter to terminals 7 (+) and 8 (-).
5. Adjust R4 until the voltmeter displays 10.0 VDC.

Figure 20

GENERIC SENSORS

Z

ERO

A

DJUSTMENT

1. Apply Power to the SC100.
2. Unload the sensor or sensors making sure their

outputs represent the minimum value or at rest
condition.

3. Connect a voltmeter to terminals 5 (+) and 6 (-).
4. Rotate Z1 until the voltmeter reads 0.025 VDC.
5. Connect a voltmeter to terminals 7 (+) and 8 (-).
6. Rotate Z2 until the voltmeter reads 0.025 VDC.

S

PAN

A

DJUSTMENT

1. Apply a known load to the sensor 1.
2. Connect a voltmeter to terminals 5 (+) and 6 (-).
3. Rotate S1 clockwise to increase the reading to the

desired voltage level for the load applied.

NOTE: If using one sensor, skip steps 4 through 6.

4. Connect a voltmeter to terminals 7 (+) and 8 (-).
5. Rotate S2 clockwise to increase the reading to the

desired voltage level for the load applied.

6. Repeat

the

Zero Adjustment and Span Adjustment

procedures detailed above.

NOTE: Span Adjustments procedures may offset the
Zero Adjustment settings. Repeating both procedures
will ensure that settings are accurate.

7. Set the Output Mode switch to the desired setting,

either Individual or Summed (See Switch Settings in
SETUP section).

6. Repeat

the

Zero Adjustment and Span Adjustment

procedures detailed above.

NOTE: Span Adjustments procedures may offset the
Zero Adjustment settings. Repeating both procedures
will ensure that settings are accurate.

7. Set the Output Mode switch to the desired setting,

either Individual or Summed (See Switch Settings in
SETUP section).

Problem

Possible Cause

Quick Test

Corrective Action

Power LED is not lit.

No power or incorrect
power to SC100

Test terminal 1 (+) and terminal 2 (-)
with a voltmeter.

Check wire connections and/or
replace power supply.

SC100 Output does

not change with load.

Incorrect power

supply connections

Test terminals 1 (+) and 2 (-) and
terminals 3 (+) and 4 (-) with a
voltmeter.

Check wire connections and/or
replace power supply.

Sensor inputs wired
backwards

Test terminals 9 (+) and 10 (-) and
terminals 15 (+) and 16 (-) with a
voltmeter.

If test shows a negative voltage,

swap sensor leads.

Incorrect excitation

voltage

Compare adjustable excitation

voltage with sensor specifications.

Adjust excitation voltage

potentiometer for correct voltage.

Incorrect polarity on

SW sensors.

Refer to Sensor Connections
Diagrams.

Check wire connections; make
sure red and black wires are
swapped on the No. 2 sensor.

Span does not reach

required voltage level.

Wrong GAIN

setting

Refer to Switch

Settings.

Switch the input GAIN

switch

and adjust span potentiometer.