7 operation, 1 display elements, 1 display elements for device diagnostics – Pilz PSSnet GW1 MOD-CAN User Manual
Page 35: Section 7, Operation, Display elements, Display elements for device diagnostics
Operation
Operating Manual PSSnet GW1 MOD-CAN
1002693-EN-02
35
Operation
Display elements
Status LEDs on the front provide information on the module's activity.
LED on
LED flashes
LED flashes briefly
1
LED flashes once periodically
2
LED flashes twice periodically
3
LED flashes tree times periodically
LED off
LED display symbols
Display elements for device diagnostics
LED
LED status
Meaning
Pwr/Stat
Green
Fault-free operation
Red
Internal error (module error) or IP address
conflict
No supply voltage or device is defective
LED
LED status
Meaning
Link/Trf
Green
Link present, 100 Mbit/s
Green
Traffic present, 100 Mbit/s
Red
Max. 15 sec. after power-up: Still waiting for
answer from DHCP Server.
After more than 15 sec.: The default IP ad-
dress 192.168.0.1 is already used in the net-
work. In this case the module cannot be
reached via Ethernet.
Red
No Modbus/TCP connection
Red
Incorrect Register range (during Client re-
quest)
Orange
Link present, 10 Mbit/s
Orange
Traffic present, 10 Mbit/s
No link