Operation

Operating Manual PSSnet GW1 MOD-CAN
1002693-EN-02

35

Operation

Display elements

Status LEDs on the front provide information on the module's activity.

LED on

LED flashes
LED flashes briefly

1

LED flashes once periodically

2

LED flashes twice periodically

3

LED flashes tree times periodically

LED off

LED display symbols

Display elements for device diagnostics

LED

LED status

Meaning

Pwr/Stat

Green

Fault-free operation

Red

Internal error (module error) or IP address

conflict
No supply voltage or device is defective

LED

LED status

Meaning

Link/Trf

Green

Link present, 100 Mbit/s

Green

Traffic present, 100 Mbit/s

Red

Max. 15 sec. after power-up: Still waiting for

answer from DHCP Server.

After more than 15 sec.: The default IP ad-

dress 192.168.0.1 is already used in the net-

work. In this case the module cannot be

reached via Ethernet.

Red

No Modbus/TCP connection

Red

Incorrect Register range (during Client re-

quest)

Orange

Link present, 10 Mbit/s

Orange

Traffic present, 10 Mbit/s
No link