beautypg.com

1 block diagram, 2 modbus/tcp, 1 modbus/tcp data ranges (server connections) – Pilz PSSnet GW1 MOD-CAN User Manual

Page 17: Block diagram, Modbus/tcp, Modbus/tcp data ranges (server connections)

background image

Function description

Operating Manual PSSnet GW1 MOD-CAN
1002693-EN-02

17

Block diagram

Connection to

Modbus/TCP

1x CANopen

24 V 0 V

Mapping

Power

Block diagram

Modbus/TCP

The Gateway can manage a max. of 8 Modbus/TCP connections. The Gateway is always
the connection Server. The connection Clients may be various devices, e.g. PC, control
system, display unit. They can access the Gateway simultaneously.
Port number "502" in the Gateway is set as the default for data exchange via a Modbus/
TCP connection.

Modbus/TCP data ranges (Server connections)

The product supports the following Modbus/TCP data areas:

Data area

Modbus syntax

Example

Coils (Bit)

0x00000 … 0x65535

[read/write]

0x[xxxxx]

0x00031

Discrete Inputs (Bit)

1x00000 … 1x65535

[read only]

1x[xxxxx]

1x08193

Input Register (Wort/16 Bits)

3x00000 … 3x65535

[read only]

3x[xxxxx]

3x00002

Holding Register (Wort/16

Bits)

4x00000 … 4x65535

[read/write]

4x[xxxxx]

4x00805

Modbus/TCP data areas

4.1.1

4.2

4.2.1