beautypg.com

Troubleshooting – WaterFurnace Envision Hydronic (NSW) User Manual

Page 46

background image

46

NSW INSTALLATION MANUAL

Troubleshooting

Should a major problem develop, refer to the following

information for possible causes and corrective steps:

Compressor Won’t Run

1. The fuse may be blown or the circuit breaker is open.

Check electrical circuits and motor windings for shorts or

grounds. Investigate for possible overloading. Replace

fuse or reset circuit breakers after the fault is corrected.

2. Supply voltage may be too low. Check voltage with a

volt meter.

3. Remote control system may be faulty. Check aquastat

for correct wiring, setting and calibration. Check 24-volt

transformer for burnout.

4. Wires may be loose or broken. Replace or tighten.

5. The low pressure switch may have tripped due to one or

more of the following:

a. Fouled or plugged coaxial heat exchangers

b. Low or no water flow (source side heating, load

side

cooling)

c. Water too cold (source side heating)

d.

Low

refrigerant

6. The high pressure switch may have tripped due to one

or more of the following:

a. Fouled or plugged coaxial heat exchanger

b. Low or no water flow (source side cooling, load

side

heating)

c. Water too warm (source side cooling)

7. Check the capacitor.

8. The compressor overload protection may be open. If

the compressor dome is extremely hot, the overload

will not reset until cooled down. If the overload does

not reset when cool, it may be defective. If so, replace

the compressor.

9. The internal winding of the compressor motor may be

grounded to the compressor shell. If so, replace

the compressor.

10. The compressor winding may be open. Check

continuity with an ohm meter. If the winding is open,

replace the compressor.

Insufficient Cooling or Heating

1. Check aquastat for improper location (secondary

mode only).

2. Check for restriction in water flow.

3. Check subcooling for low refrigerant charge.

4. The reversing valve may be defective and creating a

bypass of refrigerant. If the unit will not cool, check the

reversing valve coil.

5. Check thermal expansion valve for possible restriction of

refrigerant flow.

Noisy Unit Operation

1. Check compressor for loosened mounting bolts. Make

sure compressor is floating free on its isolator mounts.

2. Check for tubing contact with the compressor or other

surfaces. Readjust it by bending slightly.

3. Check screws on all panels.

4. Check for chattering or humming in the contactor or

relays due to low voltage or a defective holding coil.

Replace the component.

5. Check for proper installation of vibration absorbing

material under the unit. Unit must be fully supported,

not just on corners.

6. Check for abnormally high discharge pressures.