NSW INSTALLATION MANUAL

Reference Calculations

Legend and Notes

Heating Calculations:

LWT = EWT - HE

GPM x C*

Cooling Calculations:

LWT = EWT + HR

GPM x C*

HE = C* x GPM x (EWT - LWT)

HR = C* x GPM x (LWT - EWT)

NOTE: * C = 500 for pure water, 485 for brine.

Abbreviations and Definitions

ELT

= entering load fluid temperature to heat pump

kW

= kilowatts

SWPD = source coax water pressure drop

EST

= entering source fluid temperature to heat pump

LLT

= leaving load fluid temperature from heat pump

HE

= heat extracted in MBTUH

PSI

= pressure drop in pounds per square inch

LST

= leaving source fluid temperature from heat pump

LGPM = load flow in gallons per minute

HC

= total heating capacity in MBTUH

FT HD = pressure drop in feet of head

COP = coefficient of performance, heating [HC/kW x 3.413]

LWPD = load coax water pressure drop

EER

= energy efficiency ratio, cooling

LWT

= leaving water temperature

TC

= total cooling capacity in MBTUH

EWT

= entering water temperature

HR

= heat rejected in MBTUH

Brine

= water with a freeze inhibiting solution

Notes to Performance Data Tables

The following notes apply to all performance data tables:

• Three flow rates are shown for each unit. The lowest flow rate shown is used for geothermal open loop/well water

systems with a minimum of 50°F EST. The middle flow rate shown is the minimum geothermal closed loop flow rate.

The highest flow rate shown is optimum for geothermal closed loop systems and the suggested flow rate for boiler/

tower applications.

• Entering water temperatures below 40°F assumes 15% antifreeze solution.

• Interpolation between ELT, EST, and GPM data is permissible.

• Operation in the gray areas is not recommended.