beautypg.com

Optional controls - fx10 cont – WaterFurnace Envision Hydronic (NSW) User Manual

Page 33

background image

33

NSW INSTALLATION MANUAL

FX10 Advanced Control Overview

• The Johnson Controls FX10 board is specifically designed

for commercial heat pumps and provides control of the

entire unit as well as input ports for Open N2, LonTalk,

BACnet (MS/TP @ 19,200 Baud Rate) communication

protocols as well as an input port for a user interface.

The user interface can be used to aid in diagnostics and

unit setup and is optional on all NSW units. A 16-pin low

voltage terminal board provides terminals for common

field connections. The FX10 Control provides:

• Operational sequencing

• High and low-pressure switch monitoring

• General lockout

• Freeze Detection Temperature Sensing

• Lockout mode control

• Emergency shutdown mode

• Random start and short cycle protection

Short Cycle Protection

Allows a minimum compressor “off” time of five minutes

and a minimum “on” time of two minutes.

Random Start

A delay of 1 to 120 seconds is generated after each power-

up to prevent simultaneous startup of all units within a

building after the release from an unoccupied cycle or

power loss.

Emergency Shutdown

A field-applied dry contact can be used to place the control

into emergency shutdown mode. During this mode, all

outputs on the board are disabled.

Freeze Detection Temperature Limit

Field selectable for 15°F or 30°F (-9° or -0.56°C)

Installation Options

• Standalone controlled by standard aqua stat

• Integrated into BAS by adding communication module

Accessory Outputs

Quantity 2. Cycled with the compressor. Field selectable for

normally open (factory default) or normally closed through

the building automation system or user interface.

User Interface

4 x 20 backlit LCD

Optional Plug-in Communication Modules -
(compatible with standard BAS protocols)

• Open

N2

• LonTalk

• BACnet (MS/TP @ 19,200 Baud Rate, 30 unit max per

trunk line)

Display

One local display is optional on all NSW units. Up to

2 displays, either 1 local and 1 remote, or 2 remote. (A

2-display configuration requires identical displays.) Local

display can be up to 3 meters from the controller, power

supply, and data communication. Remote display can be up

to 300 meters from the controller. Remote display must be

independently powered with data communication done via

3 pole shielded cable.

Control Timing & Fault Recognition Delays

Lead compressor “ON” delay ..........................................90 seconds

(not applicable for single compressor models)

Minimum compressor “ON” time ...................................... 2 minutes

(except for fault condition)

Short cycle delay ..................................................................... 5 minutes

Random start delay .......................................................0-120 seconds

High pressure fault ................................................................. <1 second

Low pressure fault ...............................................................30 seconds

Freeze detection fault ................................................... 0-30 seconds

Low pressure/freeze fault bypass..................................... 2 minutes

NOTES: Refer to Submittal Data SD1981, Application Guide

AGFX10, or BACnet Protocol Implementation Conformance

Statement for more information.

Optional Controls - FX10 cont.

Main FX 10 Board