beautypg.com

Operating parameters, Nsw installation manual, Heating mode – WaterFurnace Envision Hydronic (NSW) User Manual

Page 41: Cooling mode

background image

41

NSW INSTALLATION MANUAL

Operating Parameters

Heating Mode

Entering

Load Temp (°F)

Entering

Source Temp (°F)

Suction

Pressure (psig)

Discharge

Pressure (psig)

Superheat

(°F)

Subcooling

(°F)

60

20

52-67

195-227

8-16

5-15

30

67-82

208-235

7-14

6-14

50

95-113

216-245

7-14

6-12

70

124-144

225-255

8-19

5-15

90

143-167

230-275

14-26

8-12

80

20

54-69

283-316

8-16

7-15

30

69-84

293-323

10-12

7-18

50

98-125

302-335

12-14

8-16

70

121-148

311-346

14-18

8-16

90

144-179

319-363

14-26

8-16

100

20

56-71

369-405

8-10

6-14

30

77-85

378-411

10-12

7-15

50

64-126

388-425

12-14

7-15

70

123-152

398-438

14-18

3-12

90

148-191

408-452

14-22

3-12

120

20

59-74

455-495

8-18

4-16

30

74-87

464-500

6-16

5-17

50

106-128

474-515

5-17

5-15

70

125-156

485-530

6-16

4-15

90

Operation not recommended

NOTES: Operating parameters at 3 gpm/ton source and load flow. Consult the Capacity Tables for each NSW model for normal allowable operating

conditions. Some of the conditions shown above are outside of the compressor operational limits for specific models.

Cooling Mode

Entering

Load Temp (°F)

Entering

Source Temp (°F)

Suction

Pressure (psig)

Discharge

Pressure (psig)

Superheat

(°F)

Subcooling

(°F)

50

30

86-99

135-160

12-22

2-15

50

92-107

191-214

10-19

4-15

70

98-115

248-268

5-15

6-16

90

101-119

335-367

6-15

8-16

110

105-122

425-465

8-16

10-19

70

30

89-106

131-163

15-20

3-6

50

103-125

194-223

11-15

6-9

70

118-143

257-273

11-15

9-12

90

125-151

344-381

8-12

12-14

90

30

92-113

128-166

15-20

3-6

50

115-143

197-233

11-15

6-9

70

129-158

266-294

11-15

9-12

90

150-168

354-395

8-12

12-14

110

30

96-121

125-170

55-65

2-20

50

127-161

200-243

41-52

4-18

70

158-200

275-315

21-38

8-19

90

Operation not recommended

NOTES: Operating parameters at 3 gpm/ton source and load flow. Consult the Capacity Tables for each NSW model

for normal allowable operating conditions. Some of the conditions shown above are outside of the compressor

operational limits for specific models.

6/16/09