Software user manual – SurgeX EV-23010 User Manual
Page 17
Software User Manual
iv. Update ID: Sets the product identifier specified in the text box. 10
character limit.
v. Update Limits: Sets the 6 voltage thresholds specified by the voltage
threshold selection fields.
Limit
When Activated
Action
Factory Default
120V
208/240V
Over Voltage
Shutdown
V > OV
Shutdown
Outlets turned Off and
event recorded
150
280
Over Voltage
Record
OV
Shutdown
> V > OV
Record
Outlets stay On and
event recorded
145
270
Over Voltage
Restore
V < OV
Restore
After OV
Shutdown
Outlets turned On and
event recorded
140
260
Under Voltage
Restore
V > UV
Restore
After UV
Shutdown
Outlets turned On and
event recorded
105
190
Under Voltage
Record
UV
Shutdown
< V < UV
Record
Outlets stay On and
event recorded
100
180
Under Voltage
Shutdown
V < UV
Shutdown
Outlets turned Off and
event recorded
80
160
g. COM Port Setup Mode
i. The COM Port Setup mode is used to configure new Data Interface
Cables for use.
ii. Detect: Automatically detect the COM Port when the enVision, Data
Interface Cable, and PC are properly connected and powered up.
iii. Configure: Automatically configure the advanced settings of the Data
Interface Cable. May require running the software with elevated
permissions (right-click program shortcut and choose “Run As
Administrator”) on Windows Vista/7/8 with UAC (User Account
Control) enabled.
iv. Save: Saves the COM Port selection.